Powered by GoogleTranslate

Inspection Detail

Inspection: 102260031 - Red Simpson, Inc.

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 102260031
Report ID: 0625700
Date Opened: 04/15/1993

Site Address:
Red Simpson, Inc.
Louisiana Street Sub Station
Shreveport, LA 71102

Mailing Address:
Po Box 12120, Alexandria, LA 71315

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/02/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/15/1993


Related Activity
Type Activity Nr Safety Health
Accident 361126378
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $9,475 $0 $0 $0 $0 $9,475
Current Penalty $5,685 $0 $0 $0 $0 $5,685
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260020 B01 07/01/1993 08/30/1993 $2,100 $3,500 $0 I - Informal Settlement  
2. 01002 Serious 19260021 B02 07/01/1993 08/30/1993 $2,100 $3,500 $0 I - Informal Settlement  
3. 01003 Serious 19260059 E01 07/01/1993 08/30/1993 $495 $825 $0 I - Informal Settlement  
4. 01004 Serious 19260059 G01 07/01/1993 08/30/1993 $495 $825 $0 I - Informal Settlement  
5. 01005 Serious 19260059 H 07/01/1993 08/30/1993 $495 $825 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14396337
Event: 04/13/1993
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE

Two power line workers were transferring overhead power lines from an old pole to a new one. One of the power lines (a distribution line) was deenergized, while the other (a transmission line) remained energized. The deenergized line had been installed above the energized line. One of the employees was on a utility pole, and his coworker was in an aerial lift bucket. The pole was covered with grounded hardware cloth, known as bird wire. Just before the employee on the pole finished working on the deenergized line, the coworker began transferring the energized line to the new pole. The employee on the pole was just above his coworker. The come-alongs the coworker was using contacted the energized line and the bird wire at the same time, electrocuting the employee on the pole. (Attempts to revive the injured worker failed, and he was pronounced dead on arrival at a hospital.)

Keywords: ELEC PROTECT EQUIP, HAND WINCH, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102260031 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.