Inspection Detail
Inspection: 102253770 - Vernon Lofties Electrical & Refrigeration
Inspection Information - Office: Oklahoma City Area Office
Site Address:
Vernon Lofties Electrical & Refrigeration
8810 N. Harrison
Shawnee, OK 74801
Mailing Address:
Route 5, Box 408, Shawnee, OK 74801
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/26/1989
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/30/1989
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360444418 |
Investigation Summary
AN ELECTRICAL CONTRACTOR WAS INSTALLING A 480-VOLT, 10-HORSEPOWER AIR COMPRESSOR IN AN EQUIPMENT ROOM IN A GLASS TEMPERING PLANT. THERE WERE THREE CONTRACTOR EMPLOYEES ON SITE (INCLUDING THE CONTRACTOR HIMSELF), BUT THE CONTRACTOR WAS THE ONLY ELECTRICIAN. THE CONTRACTOR MADE ARRANGEMENTS WITH THE PLANT EQUIPMENT OPERATOR TO DEENERGIZE THE ELECTRICAL POWER SO THAT THE AIR COMPRESSOR COULD BE INSTALLED. THE CONTRACTOR HAD RUN CONDUIT, INSTALLED A PANELBOARD AND AN ELECTRICAL BOX FOR THE DISCONNECTING MEANS, AND PULLED AND CONNECTED ALL WIRING. THE CONTRACTOR NOTIFIED THE PLANT OPERATOR THAT HE WAS GOING TO DEENERGIZE THE POWER SO THAT HE COULD CONNECT THE COMPRESSOR. ON RETURNING TO THE EQUIPMENT ROOM TO CONNECT THE COMPRESSOR WIRING TO A 480-VOLT PANELBOARD, THE CONTRACTOR NEGLECTED TO OPERATE THE DISCONNECTING MEANS TO DEENERGIZE THE CIRCUIT. WHEN THE CONTRACTOR PLACED AN ALLEN WRENCH INTO THE PANELBOARD, HE WAS ELECTROCUTED.
Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, HAND TOOL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102253770 | Fatality | Electric Shock | Chief exec's & gen'l administrators, public admin. |