Powered by GoogleTranslate

Inspection Detail

Inspection: 102246345 - Nelson Electric

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 102246345
Report ID: 0627700
Date Opened: 02/01/1988

Site Address:
Nelson Electric
4041 S. Sheridan Rd.
Tulsa, OK 74146

Mailing Address:
P.O. Box 726, Tulsa, OK 74101

Union Status: Union

SIC:3613

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/02/1988

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 05/03/1988


Related Activity
Type Activity Nr Safety Health
Accident 360159404
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 3 9
Current Violations 6 3 9
Initial Penalty $1,240 $0 $0 $0 $0 $1,240
Current Penalty $1,240 $0 $0 $0 $0 $1,240
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100094 D09 V 03/24/1988 03/30/1988 $90 $90 $0 -  
2. 01002 Serious 19100178 K01 03/24/1988 04/01/1988 $90 $90 $0 -  
3. 01003 Serious 19100212 A03 II 03/24/1988 03/31/1988 $90 $90 $0 -  
4. 01004A Serious 19100215 B01 03/24/1988 03/31/1988 $180 $180 $0 -  
5. 01004B Serious 19100215 B09 03/24/1988 03/31/1988 $0 $0 $0 -  
6. 01005 Serious 19100252 D02 II 03/24/1988 03/31/1988 $160 $160 $0 -  
7. 01006A Serious 19100303 B01 03/24/1988 04/05/1988 $630 $630 $0 -  
8. 02001 Other 19100134 B05 03/24/1988 03/31/1988 $0 $0 $0 -  
9. 02002 Other 19100303 B02 03/24/1988 03/31/1988 $0 $0 $0 -  
10. 02003 Other 19100305 G01 I 03/24/1988 03/27/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 774984
Event: 01/27/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYER HAD FINISHED THE CONSTRUCTION OF A NEW ELECTRIC SWITCH RACK FOR A CUSTOMER--A PETROLEUM COMPANY. BEFORE DELIVERY, THE RACK HAD TO UNDERGO ELECTRICAL TESTING. THIS TESTING WAS BEING HINDERED BY A FAULTY RELAY, WHICH WAS CHATTERING. SEVERAL ATTEMPTS WERE MADE BY THE ELECTRICAL ASSEMBLY PERSONNEL TO REPAIR THE RELAY, SO THAT IT WOULD NOT HAVE TO BE REPLACED. (NO REPLACEMENTS WERE IN STOCK; ONE WOULD HAVE TO BE ORDERED.) THE EMPLOYEE PERFORMING THE TESTING, A WIRING INSPECTOR, WAS ASKED TO REPEAT THE TESTS. HE UNWOUND THE CABLES FROM THE 480-VOLT POWER SUPPLY FOR THE TEST AND DID NOT NOTICE THAT THE CONTROL FOR THE UNIT WAS IN THE "ON" POSITION. WHILE HOLDING THE CABLE LEADS IN HIS HANDS, HE DIRECTED A NEARBY ASSEMBLY WORKER TO PLUG IN THE POWER SUPPLY. THE WIRING INSPECTOR WAS ELECTROCUTED, IN SPITE OF THE FIRST AID TREATMENT HE RECEIVED. THE EMPLOYEE HAD BEEN TRAINED IN THIS TYPE OF WORK AND HAD BEEN PERFORMING IT FOR THE LAST 4 YEARS.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 102246345 Fatality Electric Shock Inspectors, testers and graders
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close