Inspection Detail
Inspection: 102096773 - Zions Securities Corp
Inspection Information - Office: Utah Division Of Occupational Safety And Health
Site Address:
Zions Securities Corp
135 Social Hall Avenue
Salt Lake City, UT 84111
Mailing Address:
55 South State Street, Slc, UT 84111
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 01/07/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 09/16/1987
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360111223 |
Investigation Summary
An apprentice electrician was installing an A-frame electrical meter. The base had been installed several years earlier. The meter base was not connected to a load, it but was still energized. As he was replacing the busbar jumpers in the meter base, an electrical fault occurred. The ensuing electric arc burned the employee on his hands and face. He was hospitalized for his injuries. According to the electric utility company, the fault occurred because the original wiring into the base was not installed correctly. The 480-volt, three-phase supply was running between two sides of one set of busbars in the meter base and thus more susceptible to faulting. In fact, the utility no longer used this type of meter base because they had experienced problems with it.
Keywords: BURN, E GI II, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, ELECTRIC METER, LOCKOUT, ELECTRICAL FAULT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 102096773 | Hospitalized injury | Burn/Scald(Heat) | Electricians' apprentices |