Powered by GoogleTranslate

Inspection Detail

Inspection: 101996221 - Hancock County Remc

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 101996221
Report ID: 0551800
Date Opened: 08/05/1986

Site Address:
Hancock County Remc
Accident - 600 E & 900 N
Greenfield, IN 46140

Mailing Address:
Po Box 188, Greenfield, IN 46140

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/25/1986

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/18/1988


Related Activity
Type Activity Nr Safety Health
Accident 360199467
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,700 $0 $0 $0 $0 $1,700
Current Penalty $1,700 $0 $0 $0 $0 $1,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260950 C01 I 09/08/1986 09/11/1986 $1,000 $1,000 $0 -  
2. 01001B Serious 19260955 C03 09/08/1986 09/11/1986 $0 $0 $0 -  
3. 01002A Serious 19260955 C05 09/08/1986 09/11/1986 $700 $700 $0 -  
4. 01002B Serious 19260955 A02 09/08/1986 09/11/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 671834
Event: 07/15/1986
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A THREE-PERSON CREW WAS REARRANGING OVERHEAD POWER LINES ALONG A ROAD. ONE OF THE LINE WORKERS WAS GOING TO TERMINATE A #2 TRIPLEX CABLE ON A UTILITY POLE LOCATED ON THE WEST SIDE OF THE ROAD. THE LINE WORKER HAD POSITIONED HIS 50-FOOT AERIAL LIFT ON THE WEST SIDE OF THE ROAD. HE PLACED THE BOOM AND BUCKET OF THE LIFT PERPENDICULAR TO THE VEHICLE, DIRECTLY UNDER A 12-KILOVOLT OVERHEAD POWER LINE THAT RAN NORTH AND SOUTH ON THE EAST SIDE OF THE ROAD. AT THIS POINT, THE LINE WORKER'S HEAD WAS ABOUT 33 FEET FROM THE 12-KILOVOLT LINE. ANOTHER CREW MEMBER HANDED THE LINE WORKER THE TRIPLEX CABLE, AND HE BEGAN TO RAISE THE BOOM AND BUCKET UPWARD. WHEN HE RAISED THE AERIAL LIFT, THE LINE WORKER CONTACTED THE 12-KILOVOLT POWER LINE WITH HIS HEAD AND CHEST AND WAS ELECTROCUTED.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101996221 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close