Inspection Detail
Inspection: 101827442 - Bill Halfacre, Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Bill Halfacre, Inc.
10563 Park Boulevard
Seminole, FL 33542
Mailing Address:
1701 Desoto Road, Sarasota, FL 33580
Union Status: NonUnion
SIC:1542
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/12/1986
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 09/12/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360706956 |
Investigation Summary
AN EMPLOYEE WAS SITTING ON A LADDER MOUNTED ON TOP OF A CRANE BOOM. THE CRANE WAS MOUNTED ON THE BACK OF A FLAT BED TRUCK. THE EMPLOYEE WAS USING A PORTABLE ELECTRIC DRILL THAT WAS CONNECTED TO A GENERATOR SITTING ON THE TRUCK. THE FRAME OF THE GENERATOR WAS NOT BONDED TO THE TRUCK, BECAUSE THE GENERATOR WAS STILL SITTING IN THE BOTTOM OF ITS SHIPPING CRATE. (THE SHIPPING CRATE WAS HOWEVER ATTACHED TO THE TRUCK BED.) A WIRE NUT INSIDE THE ELECTRIC BRAKE FOR THE CRANE HAD BROKEN, AND THE CONDUCTORS INSIDE WERE IN CONTACT WITH THE METAL COVER OF THE BRAKE. THIS ENERGIZED THE BOOM OF THE CRANE; AND THE EMPLOYEE, WHO WAS CONNECTED TO THE GENERATOR FRAME (THE SYSTEM GROUND) BY MEANS OF THE DRILL'S EQUIPMENT GROUNDING CONDUCTOR, WAS ELECTROCUTED.
Keywords: ELECTRICAL, E C, GROUND FAULT, BONDING, ELECTRIC GENERATOR, ELECTROCUTED, SYSTEM GROUNDING, ELEC EQUIPMENT--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101827442 | Occupation Not Listed |