Powered by GoogleTranslate

Inspection Detail

Inspection: 101822872 - A & E Electric Company, Inc.

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 101822872
Report ID: 0420600
Date Opened: 08/14/1987

Site Address:
A & E Electric Company, Inc.
2315 Marathon Road
Odessa, FL 33556

Mailing Address:
10731 Williams Road, Thonotossa, FL 33592

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/20/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/14/1987


Related Activity
Type Activity Nr Safety Health
Referral 901019943
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $820 $0 $0 $0 $0 $820
Current Penalty $820 $0 $0 $0 $0 $820
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 08/31/1987 09/02/1987 $640 $640 $0 -  
2. 01002A Serious 19260500 D01 08/31/1987 09/02/1987 $180 $180 $0 -  
3. 01002B Serious 19260500 E01 III 08/31/1987 09/02/1987 $0 $0 $0 -  
4. 02001 Other 19260020 B01 08/31/1987 09/08/1987 $0 $0 $0 -  
5. 02002 Other 19260403 H 08/31/1987 09/04/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14516769
Event: 08/14/1987
ELECTRIC SHOCK & BURNS - FAULT IN PANELBOARD

THREE EMPLOYEES OF AN ELECTRICAL CONTRACTOR WERE INSTALLING EQUIPMENT AND WIRING FOR A CONTROL CENTER IN AN ASPHALT PLANT UNDER CONSTRUCTION. THE POWER FOR THE PLANT HAD BEEN ENERGIZED FOR ABOUT 2 WEEKS. TWO OF THE EMPLOYEES WERE INSTALLING A LUG ON A GROUNDED BUSBAR AT THE BASE OF A PANELBOARD, WHICH CONTAINED 3 VERTICAL BUSBARS ENERGIZED AT 277 VOLTS. ONE OF THESE EMPLOYEES, A JOURNEYMAN ELECTRICIAN, WAS WORKING WITH A SCREWDRIVER; THE OTHER, AN APPRENTICE, WAS HOLDING A NUT WITH A WRENCH. THE END OF THE WRENCH CONTACTED ONE OF THE ENERGIZED BUSES, RESULTING IN AN ELECTRICAL EXPLOSION. THESE TWO EMPLOYEES RECEIVED FIRST, SECOND, AND THIRD DEGREE BURNS TO THE HANDS, ARMS, UPPER TORSO, NECK, AND HEAD. THE APPRENTICE ALSO RECEIVED AN ELECTRIC SHOCK. THEY WERE HOSPITALIZED FOR THESE INJURIES. A THIRD EMPLOYEE RECEIVED MINOR BURNS ON HIS HANDS AS HE WAS PUTTING OUT THE FIRE ON THE HAIR AND CLOTHING OF ONE OF THE OTHER TWO INJURED EMPLOYEES.

Keywords: ELECTRIC ARC, ELECTRICAL, E C, ELECTRIC SHOCK, ELECTRICAL FAULT, BURN, ELEC PROTECT EQUIP, PANELBOARD, ELECTRICAL WORK, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101822872 Hospitalized injury Electric Shock Electricians
2 101822872 Hospitalized injury Electric Shock Electricians' apprentices
3 101822872 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close