Inspection Detail
Inspection: 101777647 - Rouse & Associates
Inspection Information - Office: Jacksonville Area Office
Site Address:
Rouse & Associates
1200 Gulf Life Dr.
Jacksonville, FL 32207
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:6512
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/30/1986
Emphasis:
Case Closed: 07/30/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 901017194 | Yes |
Investigation Summary
AN EMPLOYEE WENT INTO A DECORATIVE FOUNTAIN TO CHECK A PUMP THAT WAS NOT PUMPING WATER AT A RATE HIGH ENOUGH FOR THE WATER FALL. WHEN THE EMPLOYEE OPENED A VALVE FOR THE PUMP, HE RECEIVED A SEVERE ELECTRIC SHOCK, FOR WHICH HE WAS HOSPITALIZED. THE EQUIPMENT GROUNDING CONDUCTOR FOR THE PUMP WAS NOT CONNECTED TO THE CIRCUIT GROUNDING CONDUCTOR. ADDITIONALLY, THE CIRCUIT CONDUCTORS FOR THE GROUND-FAULT CIRCUIT INTERRUPTER WERE REVERSED.
Keywords: ELECTRICAL, E GI VII, ELECTRIC PUMP, GROUND FAULT, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101777647 | Hospitalized injury | Electric Shock | Occupation not reported |