Inspection Detail
Inspection: 101762946 - Central Illinois Public Service
Inspection Information - Office: Peoria Area Office
Site Address:
Central Illinois Public Service
Murdock Substation
Murdock, IL 61941
Mailing Address:
711 S. 9th Street, Mattoon, IL 60443
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 06/19/1986
Emphasis:
Case Closed: 06/29/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360542740 |
Investigation Summary
AN EMPLOYEE WAS WORKING FROM AN AERIAL LIFT, GROUNDING THE LINE SIDE OF AN OIL CIRCUIT BREAKER. HE POSITIONED THE BUCKET BETWEEN THE SOUTH PHASE AND THE CENTER PHASE AND HAD ATTACHED ONE END OF THE PROTECTIVE GROUND TO THE STEEL STRUCTURE SERVING AS GROUND. THE GROUNDING CABLE PASSED BETWEEN THE INSULATOR AND THE BLADE OF A SWITCH. THIS POSITION WOULD HAVE INTERFERED WITH THE REMOVAL OF THE SWITCH. THERE WERE NO WITNESSES TO THE ACCIDENT, BUT IT WAS APPARENT THAT THE EMPLOYEE TRIED TO PASS THE LOOSE END OF THE GROUNDING CABLE AROUND THE BLADE OF THE SWITCH. IN SO DOING, HE APPARENTLY CONTACTED THE ENERGIZED BLADE OF THE SWITCH AND WAS ELECTROCUTED.
Keywords: ELEC PROTECT EQUIP, PROTECTIVE GROUNDING, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, ELECTROCUTED, E PTD, CIRCUIT BREAKER, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101762946 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate