Inspection Detail
Inspection: 101634103 - Crown Zellerback Corporation
Inspection Information - Office: Baton Rouge Area Office
Site Address:
Crown Zellerback Corporation
Hwy 964
St. Francisville, LA 70775
Mailing Address:
P. O. Box 218, St. Francisville, LA 70775
Union Status: Union
SIC:2621
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/12/1987
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 06/30/1987
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360135644 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $640 | $0 | $0 | $0 | $0 | $640 |
Current Penalty | $640 | $0 | $0 | $0 | $0 | $640 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100303 B01 | 06/08/1987 | 06/11/1987 | $640 | $640 | $0 | - |
Investigation Summary
A superintendent for a construction company asked a plant maintenance electrician to hook up a welding machine. The electrician cut the plug off of the machine and thinking the machine was a three-phase unit connected each of the conductors (black, white, and green) directly to one phase of a three-phase circuit in a panelboard. The welding machine was actually a 240-volt, single-phase unit, and the green conductor was an equipment grounding conductor and was connected to the case of the machine. When the electrician connected the equipment grounding conductor to the 277-volt bus, the metal case of the welding machine became energized. The superintendent was electrocuted when he touched the welding machine. Another nearby employee, who was trying to help the injured worker, touched the machine and received an electric shock.
Keywords: ELECTRICAL, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC SHOCK, UNTRAINED, E GI V, ELECTRICIAN, ELECTROCUTED, PANELBOARD
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 101634103 | Occupation Not Listed |