Powered by GoogleTranslate

Inspection Detail

Inspection: 101557395 - Yazoo Valley-Minter City Oil Mill, Inc.

Inspection Information - Office: Jackson Area Office

 

Inspection Nr: 101557395
Report ID: 0419400
Date Opened: 10/07/1986

Site Address:
Yazoo Valley-Minter City Oil Mill, Inc.
2015 West River Road
Greenwood, MS 38930

Mailing Address:
P. O. Box 1320, Greenwood, MS 38930

Union Status: Union

SIC:2074

NAICS: 0 


Inspection Type: Complaint

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/10/1986

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 03/02/1987


Related Activity
Type Activity Nr Safety Health
Complaint 71207278 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $700 $0 $1,400 $0 $0 $2,100
Current Penalty $450 $0 $900 $0 $0 $1,350
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 11/19/1986 02/09/1987 $450 $700 $0 I - Informal Settlement  
2. 02001 Repeat 19100307 B 11/19/1986 02/09/1987 $900 $1,400 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14340186
Event: 10/07/1986
EMPLOYEES BURNED BY HEXANE VAPOR FIRE

AN EMERGENCY BREAKDOWN AT THE COTTONSEED OIL SOLVENT EXTRACTOR MADE THE REMOVAL OF LIQUID HEXANE AND HEXANE VAPORS FROM THE EXTRACTOR AND EXTRACTOR BUILDING NECESSARY. SOME LIQUID HEXANE REMAINED IN THE PUMPING LINES BETWEEN THE EXTRACTOR SUMPS AND PUMPS THREE HOURS AFTER THE BREAKDOWN. THREADED DRAIN CAPS IN THE PUMPING LINES HAD BEEN PREMATURELY REMOVED, ALLOWING HEXANE TO DRIP ONTO THE FIRST FLOOR CONCRETE SURFACE. EMPLOYEES #1 AND #2 WERE ATTEMPTING TO CONNECT A FLEXIBLE METAL PIPE TO THE SIDE OF AN EXTRACTOR FROM THE INLET PORT OF A PORTABLE ELECTRIC PURGE FAN. THE FAN WAS TO BE USED TO DRAW HEXANE VAPORS OUT OF THE EXTRACTOR, SO THAT EMPLOYEES COULD ENTER THE AREA. HEXANE VAPORS WERE IGNITED JUST ABOVE THE FAN'S STARTER AND SWITCH. EMPLOYEES #1 AND #2 RECEIVED FIRST, SECOND AND THIRD DEGREE BURNS. AN INVESTIGATION REVEALED EVIDENCE OF ARCING AMONG CONDUCTORS INSIDE A NON-EXPLOSION PROOF JUNCTION BOX, AND THE FAN'S STARTER ENCLOSURE COVER WAS MISSING SOME OF ITS BOLTS.

Keywords: BURN, ELECTRIC ARC, FAN, FLAMMABLE VAPORS, FIRE, HEXANE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101557395 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 101557395 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close