Powered by GoogleTranslate

Inspection Detail

Inspection: 101483311 - Armor Elevator Co., Inc.

Inspection Information - Office: Manhattan Area Office

 

Inspection Nr: 101483311
Report ID: 0215000
Date Opened: 12/31/1992

Site Address:
Armor Elevator Co., Inc.
605 3rd Avenue
New York, NY 10158

Mailing Address:
35 West 44th Street, New York, NY 10036

Union Status: Union

SIC:1796

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/08/1993

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 06/24/1993


Related Activity
Type Activity Nr Safety Health
Accident 360861736
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $17,100 $0 $0 $0 $0 $17,100
Current Penalty $11,970 $0 $0 $0 $0 $11,970
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260102 A01 05/18/1993 05/26/1993 $1,575 $2,250 $0 I - Informal Settlement  
2. 01002 Serious 19260405 B01 05/18/1993 05/21/1993 $945 $1,350 $0 I - Informal Settlement  
3. 01003 Serious 19260405 J04 IVB 05/18/1993 05/26/1993 $3,150 $4,500 $0 I - Informal Settlement  
4. 01004 Serious 19260416 A01 05/18/1993 05/26/1993 $3,150 $4,500 $0 I - Informal Settlement  
5. 01005 Serious 19260416 A03 05/18/1993 05/26/1993 $3,150 $4,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 645440
Event: 12/30/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN ELEVATOR MECHANIC WAS TROUBLESHOOTING A PROBLEM IN AN ELEVATOR CONTROL PANEL LOCATED IN AN ELEVATOR CONTROL ROOM. THE PANEL CONTAINED CIRCUIT PARTS ENERGIZED AT VOLTAGES UP TO 111 VOLTS DC AND 240 VOLTS AC. THE EMPLOYEE CONTACTED AN ENERGIZED PART WITH HIS HEAD WHILE HIS HANDS WERE GROUNDED. THE EMPLOYEE WAS ELECTROCUTED. (THE CURRENT ENTRY AND EXIT POINTS WERE FOUND DURING AN AUTOPSY.)

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTROCUTED, MECHANIC, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101483311 Fatality Electric Shock Elevator installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close