Inspection Detail
Inspection: 101475580 - U. Gaines Electric Company, Inc.
Inspection Information - Office: Baton Rouge Area Office
Site Address:
U. Gaines Electric Company, Inc.
16446 Chef Menteur Highway
New Orleans, LA 70129
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 09/27/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 07/09/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360136030 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 1 | 4 | |||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $1,890 | $0 | $0 | $0 | $0 | $1,890 |
| Current Penalty | $1,320 | $0 | $0 | $0 | $0 | $1,320 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260021 B02 | 12/13/1988 | 01/10/1989 | $440 | $630 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19260416 A01 | 12/13/1988 | 01/10/1989 | $440 | $630 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19260416 D | 12/13/1988 | 01/10/1989 | $440 | $630 | $0 | I - Informal Settlement | ||
| 4. | 02001 | Other | 19040008 | 12/13/1988 | 12/23/1988 | $0 | $0 | $0 | - |
Investigation Summary
An electrician for an electrical contractor met the treasurer of a general contractor to deenergize one building in an existing apartment complex under construction. The electrician disconnected the transformer from the primary line using a pair of electrical pliers rated at 600 volts. He then disconnected two conductors from the 120/240-volt load side. He checked the meters on he building and then told the treasurer that he was going to reenergize the system to be sure that he had correctly deenergized the building. He reconnected the transformer to the 13.8-kilovolt primary and began to insert the primary fuses using the pliers. He had some difficulty inserting the fuses and was electrocuted as he was doing so. The ground was wet from a previous rain, and the employee had no rubber insulating gloves or mat.
Keywords: FUSE, ELEC PROTECT EQUIP, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, E C, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101475580 | Fatality | Electric Shock | Electricians |