Powered by GoogleTranslate

Inspection Detail

Inspection: 101473007 - Sunbelt Plastics

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 101473007
Report ID: 0625700
Date Opened: 09/18/1989

Site Address:
Sunbelt Plastics
4611 Central Ave.
Monroe, LA 71203

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2673

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/18/1989

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 11/08/1989


Related Activity
Type Activity Nr Safety Health
Accident 360136923
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $1,880 $0 $0 $0 $0 $1,880
Current Penalty $1,880 $0 $0 $0 $0 $1,880
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 10/11/1989 10/17/1989 $640 $640 $0 -  
2. 01002 Serious 19100304 F05 V 10/11/1989 10/17/1989 $640 $640 $0 -  
3. 01003 Serious 19101200 E01 10/11/1989 11/17/1989 $300 $300 $0 -  
4. 01004 Serious 19101200 H 10/11/1989 11/17/1989 $300 $300 $0 -  

Investigation Summary

Investigation Nr: 14394704
Event: 09/13/1989
ELECTRIC SHOCK - GROUND FAULT IN ELECTRICAL BOX

A LABORER WAS CLEANING AROUND TWO WINDER MACHINES. A WITNESS SAW SOMETHING WRONG--THE LABORER WAS NOT MOVING. ANOTHER EMPLOYEE TOUCHED THE LABORER AND RECEIVED AN ELECTRIC SHOCK. THE WITNESS DEENERGIZED THE MACHINE, AND THE INJURED EMPLOYEE WAS LAID ON THE CONCRETE FLOOR. INVESTIGATION REVEALED THAT THE ELECTRICAL DISCONNECT BOX ON THE 480-VOLT MACHINE CONTAINED A BLACK CIRCUIT CONDUCTOR THAT WAS FRAYED. THERE WERE BURN MARKS INSIDE THE BOX, INDICATING THAT AN ELECTRICAL FAULT HAD OCCURRED. THE EQUIPMENT GROUNDING CONDUCTOR WAS NOT CONNECTED (IT MAY HAVE VIBRATED LOOSE). THE ENTIRE MACHINE WAS METAL AND WAS SITTING ON THE CONCRETE FLOOR. THE INJURED EMPLOYEE APPARENTLY BENT OVER AND, WHEN HE RAISED BACK UP, CONTACTED AN IDLE ROLLER. WHEN HE DID THIS, HE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRICAL BOX, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101473007 Fatality Electric Shock Laborers, except construction
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.