Powered by GoogleTranslate

Inspection Detail

Inspection: 101432060 - Texas New Mexico Power Company

Inspection Information - Office: Fort Worth Area Office

 

Inspection Nr: 101432060
Report ID: 0636900
Date Opened: 09/23/1988

Site Address:
Texas New Mexico Power Company
1304 N. Ave. G, (N. Hwy. 6)
Clifton, TX 76634

Mailing Address:
2 Miles N. Of Meridian, Hwy. 144, Meridian, TX 76634

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/26/1988

Emphasis:

Case Closed: 12/15/1988


Related Activity
Type Activity Nr Safety Health
Accident 360344519
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,400 $0 $0 $0 $0 $1,400
Current Penalty $1,400 $0 $0 $0 $0 $1,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260955 A02 11/21/1988 12/02/1988 $800 $800 $0 -  
2. 01002 Serious 19260955 A04 11/21/1988 12/02/1988 $600 $600 $0 -  

Investigation Summary

Investigation Nr: 14466049
Event: 09/21/1988
FALL - ROTTED UTILITY POLE FAILED

A utility pole was being retired after about 60 years in service. The company had tested the integrity of the pole by sounding it, that is, the pole was struck above ground with a hammer, and the resulting sounds were evaluated. The pole was determined to be solid with this method despite the fact that the company's safety manual required digging 254 millimeters below ground level and sounding, with further checks based on the quality of the initial testing. This rule had been routinely violated for several years. Two power line workers climbed this pole to release the overhead power lines it supported. The pole, which was guyed on the side opposite to where the lines were attached, was rotten just below ground level. When the employees released the tension on the pole from the power lines, the pole shifted and broke where it had rotted. Both employees fell to the ground. One of them died of his injuries. The other employee sustained injuries for which he was hospitalized.

Keywords: DISMANTLING, POWER LINE WORKER, WORK RULES, EQUIPMENT FAILURE, ELEC UTILITY WORK, FALL, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101432060 Fatality Bruise/Contus/Abras Electrical power installers and repairers
2 101432060 Hospitalized injury Bruise/Contus/Abras Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close