Inspection: 101408292 - Co-Bar Corporation

Inspection Information - Office: Toledo Area Office

 

Inspection Nr: 101408292
Report ID: 0524700
Date Opened: 04/07/1988

Site Address:
Co-Bar Corporation
1700 Landis Avenue
Oregon, OH 43616

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3316

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/14/1988

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/06/1988


Related Activity
Type Activity Nr Safety Health
Accident 360715247
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 6 7
Current Violations 1 6 7
Initial Penalty $360 $0 $0 $0 $0 $360
Current Penalty $200 $0 $0 $0 $0 $200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100023 C01 05/12/1988 05/31/1988 $200 $360 $0 I - Informal Settlement  
2. 01001B Serious 19100027 D03 05/12/1988 05/31/1988 $0 $0 $0 -  
3. 02001 Other 19030002 A01 05/12/1988 05/15/1988 $0 $0 $0 -  
4. 02002 Other 19040002 A 05/12/1988 05/31/1988 $0 $0 $0 -  
5. 02003 Other 19100022 D01 05/16/1988 06/02/1988 $0 $0 $0 -  
6. 02004 Other 19100219 C02 I 05/12/1988 05/23/1988 $0 $0 $0 -  
7. 02005 Other 19101200 E01 05/12/1988 07/18/1988 $0 $0 $0 -  
8. 02006 Other 19101200 H 05/12/1988 07/18/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14570568
Event: 04/06/1988
ELECTRIC SHOCK - GROUND FAULT IN ATTACHMENT PLUG

AN EMPLOYEE WAS USING A PORTABLE ELECTRICALLY POWERED HYDRAULIC SHEAR AND STRAIGHTENER TO STRAIGHTEN OUT A PIECE OF COIL BAR. THE EMPLOYEE HAD CONNECTED THE HUBBELL TWIST LOCK ATTACHMENT PLUG AND WAS HOLDING THE 480-VOLT TOOL IN HIS LEFT HAND. HE WALKED OVER TO THE COIL BAR AND GRABBED IT WITH HIS RIGHT HAND. THE COIL BAR WAS GROUNDED. THE ATTACHMENT PLUG FOR THE ELECTRIC TOOL HAD A GROUND FAULT--THE EQUIPMENT GROUNDING CONDUCTOR IN THE PLUG HAD COME LOOSE FROM ITS TERMINAL AND WAS CONTACTING ONE OF THE PHASE CONDUCTORS. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101408292 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.