Powered by GoogleTranslate

Inspection Detail

Inspection: 101407161 - Statler Tissue Company

Inspection Information - Office: Augusta Area Office

 

Inspection Nr: 101407161
Report ID: 0111100
Date Opened: 08/21/1987

Site Address:
Statler Tissue Company
Maple Street
Augusta, ME 04330

Mailing Address:
, , 00000

Union Status: Union

SIC:2621

NAICS: 0 


Inspection Type: Complaint

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/13/1987

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/09/1989


Related Activity
Type Activity Nr Safety Health
Complaint 72144397 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $490 $0 $0 $0 $0 $490
Current Penalty $270 $0 $0 $0 $0 $270
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 5A0001 12/08/1987 12/14/1987 $270 $490 $0 I - Informal Settlement  
2. 01001B Serious 19100134 E02 12/08/1987 12/14/1987 $0 $0 $0 -  
3. 01001C Serious 19100261 B05 12/08/1987 12/14/1987 $0 $0 $0 12/30/1987 -  
4. 01001D Serious 19101200 H02 I 12/08/1987 12/14/1987 $0 $0 $0 -  
5. 01001E Serious 19101200 H02 II 12/08/1987 12/14/1987 $0 $0 $0 -  
6. 01001F Serious 19101200 H02 III 12/08/1987 12/14/1987 $0 $0 $0 -  
7. 01001G Serious 19101200 H02 IV 12/08/1987 12/14/1987 $0 $0 $0 -  
8. 02001 Other 19100261 B05 12/08/1987 12/14/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14478291
Event: 08/21/1987
Employees affected by gases in confined space

At 9:45 a.m. on August 20, 1987, Employees #1 and #2 were in an approximately 10 ft by 6 ft by 5 1/2 ft space, cleaning soot from the tubes in a boiler air preheater. There was an induced draft fan between the air preheater and stack gas header duct. Three other boilers, two of which were operating, shared the header duct. Due to the high air demand from cleaning the boiler burners and the startup of a paper machine, a positive pressure was created in the header, forcing stack gases from the online boilers (sulfur dioxide, carbon dioxide, and nitrous oxide) into the space where the employees were working. They had been provided only with dust respirators and the gases forced them out of the confined space. Both employees were sent to the hospital and released; one of them lost work days as a result of the accident.

Keywords: MAINTENANCE, WORK RULES, BOILER, CLEANING, INHALATION, SULFUR DIOXIDE, CARBON DIOXIDE, CHEMICAL VAPOR, NITROUS OXIDE, RESPIRATOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101407161 Non Hospitalized injury Other Occupation not reported
2 101407161 Non Hospitalized injury Other Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.