Inspection Detail
Inspection: 101373686 - George Hauck Co.
Inspection Information - Office: Cincinnati Area Office
Site Address:
George Hauck Co.
4122 E. National Rd.
Springfield, OH 45504
Mailing Address:
331 W. Main St., Springfield, OH 45504
Union Status: NonUnion
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/11/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 05/18/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360649263 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 8 | 3 | 11 | |||
Current Violations | 8 | 3 | 11 | |||
Initial Penalty | $3,240 | $0 | $0 | $120 | $0 | $3,360 |
Current Penalty | $2,360 | $0 | $0 | $0 | $0 | $2,360 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260020 B02 | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
2. | 01002 | Serious | 19260021 B02 | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
3. | 01003 | Serious | 19260403 A | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
4. | 01004 | Serious | 19260403 I02 II | 09/11/1987 | 03/14/1988 | $250 | $360 | $0 | 10/01/1987 | F - Formal Settlement | |
5. | 01005 | Serious | 19260404 B01 I | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
6. | 01006 | Serious | 19260404 F06 | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
7. | 01007A | Serious | 19260405 A02 IIG | 09/11/1987 | 03/14/1988 | $310 | $420 | $0 | 10/01/1987 | F - Formal Settlement | |
8. | 01007B | Serious | 19260405 J02 II | 09/11/1987 | 03/14/1988 | $0 | $0 | $0 | 10/01/1987 | F - Formal Settlement | |
9. | 01008 | Serious | 19260416 E01 | 09/11/1987 | 03/14/1988 | $250 | $360 | $0 | 10/01/1987 | F - Formal Settlement | |
10. | 02001 | Other | 19030002 A01 | 09/11/1987 | 03/14/1988 | $0 | $60 | $0 | 10/01/1987 | F - Formal Settlement | |
11. | 02002 | Other | 19040002 B02 | 09/11/1987 | 03/14/1988 | $0 | $60 | $0 | 10/01/1987 | F - Formal Settlement | |
12. | 02003 | Other | 19260405 G02 IV | 09/11/1987 | 03/14/1988 | $0 | $0 | $0 | 10/01/1987 | F - Formal Settlement |
Investigation Summary
TWO EMPLOYEES, A JOURNEYMAN HEATING, VENTILATION, AND AIR CONDITIONING MECHANIC AND HIS APPRENTICE, WERE INSTALLING A METAL DUCT IN A CRAWL SPACE UNDER A RESIDENCE. THE MECHANIC WAS PUTTING A METAL ELBOW INTO THE DUCTWORK WHILE HE WAS KNEELING ON A DOUBLE-INSULATED DRILL AND A TROUBLE LIGHT CORD. THE DRILL WAS PLUGGED INTO A RECEPTACLE ON THE TROUBLE LIGHT. THE CORD FOR THE LIGHT WAS, IN TURN, CONNECTED TO AN EXTERIOR RECEPTACLE OUTLET OF AN ADJACENT RESIDENCE THROUGH TWO THREE-WIRE EXTENSION CORD SETS AND A SECTION OF NONMETALLIC-SHEATHED CABLE. THE CORD PASSED THROUGH A DOORWAY ON ITS WAY TO THE CRAWL SPACE. THE BLADES FOR THE EQUIPMENT GROUNDING CONDUCTOR WERE MISSING FROM THE ATTACHMENT PLUGS OF BOTH EXTENSION CORD SETS, AND THE CABLE WAS UNGROUNDED. IT APPEARED THAT THE MECHANIC'S WET CLOTHES CONTACTED ENERGIZED PARTS OF THE CORD AND PLUG CONNECTION THROUGH A DEFECT IN THE INSULATION ON THE CONDUCTORS. THE MECHANIC, WHO WAS IN CONTACT WITH THE GROUNDED METAL DUCTWORK, WAS ELECTROCUTED.
Keywords: ELEC INSULATION, ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CORD, ELECTRIC LIGHT--PORT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 101373686 | Fatality | Electric Shock | Heating, air conditioning, and refrig. mechanics |