Inspection Detail
Inspection: 101272532 - Fluor Constructors, Incorporated
Inspection Information - Office: Tampa Area Office
Site Address:
Fluor Constructors, Incorporated
Cr-3, Power Line Road
Crystal River, FL 32629
Mailing Address:
, , 00000
Union Status: Union
SIC:1796
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/16/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 02/25/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360728232 | ||
| Complaint | 70541826 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $720 | $0 | $0 | $0 | $0 | $720 |
| Current Penalty | $720 | $0 | $0 | $0 | $0 | $720 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 5A0001 | 01/28/1988 | 01/31/1988 | $720 | $720 | $0 | I - Informal Settlement |
Investigation Summary
A CONTRACTOR WAS PERFORMING WORK FOR AN ELECTRIC UTILITY AT A GENERATION STATION THAT WAS UNDERGOING A MAINTENANCE. THE PLANT WAS NOT PRODUCING ELECTRICITY DURING THE MAINTENANCE OUTAGE. A WORK STATION HAD BEEN ESTABLISHED ADJACENT TO A TRANSFORMER INSIDE A SUBSTATION AT THE PLANT. THE EMPLOYEES WHO WERE TO PERFORM THE WORK IN THE SUBSTATION WERE NOT QUALIFIED ELECTRICAL WORKERS, BUT THEIR EMPLOYER HAD THEM ENTER THE WORK AREA IN THE BELIEF THAT THE SUBSTATION HAD BEEN DEENERGIZED. HOWEVER, THE TRANSFORMERS IN THE SUBSTATION WERE ENERGIZED TO PROVIDE ELECTRICITY TO THE GENERATING PLANT, AND NO ONE HAD TESTED THE INSTALLATION TO ENSURE THAT THE WORK AREA WAS DEENERGIZED. TWO EMPLOYEES RECEIVED ELECTRIC SHOCKS AND BURNS WHEN A METAL POLE THEY WERE HANDLING CONTACTED (OR CAME TOO CLOSE TO) AN EXPOSED PART ENERGIZED AT 230 KILOVOLTS. ONE OF THE EMPLOYEES WAS ELECTROCUTED; THE OTHER WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: BURN, E GI IV, ELECTRICAL, ELECTROCUTED, LOCKOUT, METAL POLE, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, TRANSFORMER
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101272532 | Hospitalized injury | Electric Shock | Occupation not reported | ||
| 2 | 101272532 | Fatality | Electric Shock | Occupation not reported |
Translate