Inspection: 101272532 - Fluor Constructors, Incorporated

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 101272532
Report ID: 0420600
Date Opened: 10/22/1987

Site Address:
Fluor Constructors, Incorporated
Cr-3, Power Line Road
Crystal River, FL 32629

Mailing Address:
, , 00000

Union Status: Union

SIC:1796

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/16/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/25/1988


Related Activity
Type Activity Nr Safety Health
Accident 360728232
Complaint 70541826 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $720 $0 $0 $0 $0 $720
Current Penalty $720 $0 $0 $0 $0 $720
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 01/28/1988 01/31/1988 $720 $720 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14516918
Event: 10/16/1987
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU METAL POLE

A CONTRACTOR WAS PERFORMING WORK FOR AN ELECTRIC UTILITY AT A GENERATION STATION THAT WAS UNDERGOING A MAINTENANCE. THE PLANT WAS NOT PRODUCING ELECTRICITY DURING THE MAINTENANCE OUTAGE. A WORK STATION HAD BEEN ESTABLISHED ADJACENT TO A TRANSFORMER INSIDE A SUBSTATION AT THE PLANT. THE EMPLOYEES WHO WERE TO PERFORM THE WORK IN THE SUBSTATION WERE NOT QUALIFIED ELECTRICAL WORKERS, BUT THEIR EMPLOYER HAD THEM ENTER THE WORK AREA IN THE BELIEF THAT THE SUBSTATION HAD BEEN DEENERGIZED. HOWEVER, THE TRANSFORMERS IN THE SUBSTATION WERE ENERGIZED TO PROVIDE ELECTRICITY TO THE GENERATING PLANT, AND NO ONE HAD TESTED THE INSTALLATION TO ENSURE THAT THE WORK AREA WAS DEENERGIZED. TWO EMPLOYEES RECEIVED ELECTRIC SHOCKS AND BURNS WHEN A METAL POLE THEY WERE HANDLING CONTACTED (OR CAME TOO CLOSE TO) AN EXPOSED PART ENERGIZED AT 230 KILOVOLTS. ONE OF THE EMPLOYEES WAS ELECTROCUTED; THE OTHER WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: BURN, E GI IV, ELECTRICAL, ELECTROCUTED, LOCKOUT, METAL POLE, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101272532 Hospitalized injury Electric Shock Occupation not reported
2 101272532 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.