Powered by GoogleTranslate

Inspection Detail

Inspection: 101216174 - H E C, Inc.

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 101216174
Report ID: 0418100
Date Opened: 07/27/1987

Site Address:
H E C, Inc.
1955 Lake Park Drive Suite 400
Smyrna, GA 30080

Mailing Address:
2980 Angelette Road, Austell, GA 30001

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/26/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/29/1987


Related Activity
Type Activity Nr Safety Health
Accident 360126262
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $280 $0 $0 $0 $0 $280
Current Penalty $280 $0 $0 $0 $0 $280
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A01 09/02/1987 09/28/1987 $280 $280 $0 -  
2. 01001B Serious 19260417 A 09/02/1987 09/28/1987 $0 $0 $0 -  
3. 02001 Other 19260404 B01 II 09/02/1987 09/07/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 606962
Event: 07/27/1987
ELECTRIC SHOCK - CONTACT WITH LIVE CONDUCTOR THRU STRIPPER

AN ELECTRICIAN WAS WORKING IN A BUILDING UNDER CONSTRUCTION. THE EXTERIOR OF THE BUILDING WAS COMPLETED, AND THE OFFICE SPACES INSIDE WERE BEING FINISHED AS TENANTS WERE FOUND. THE ELECTRICIAN WAS WORKING WITH THE FOREMAN (HIS FATHER), WIRING A JUNCTION BOX IN THE CEILING OF ONE OF THE OFFICES. HE WAS STANDING ON A FIBERGLASS LADDER, BUT THERE WAS METAL CONDUIT BEHIND HIM AND METAL FRAMES FOR THE CEILING TILES ALL AROUND HIM. THE POWER WAS ON; AND, WHEN THE FOREMAN SAW HIM, HE TOLD HIS SON TO DEENERGIZE THE CIRCUIT BECAUSE THE WORK SPACE WAS SO TIGHT. THE ELECTRICIAN CUT INTO A CONDUCTOR ENERGIZED AT 277 VOLTS. THE HANDLES OF THE WIRE STRIPPER HE WAS USING WERE RUBBER, BUT THE WIRE STRIPPER WAS NOT OF THE INSULATED TYPE. WHEN THE ELECTRICIAN'S SCREAM WAS HEARD, THE FOREMAN AND ONE OTHER EMPLOYEE CAME INTO THE ROOM TO FIND THE ELECTRICIAN FROZEN TO THE CONDUCTOR. AFTER KICKING THE LADDER OUT FROM UNDER THE EMPLOYEE FAILED TO BREAK HIS GRIP, THE OTHER TWO PULLED THE ELECTRICIAN DOWN. THE ELECTRICIAN WAS ELECTROCUTED. ADDITIONALLY, BECAUSE OF THE STRESS INVOLVED, THE ELECTRICIAN'S FATHER (THE FOREMAN) WAS ALSO HOSPITALIZED TO PREVENT A HEART ATTACH FROM AN EXISTING HEART CONDITION. (THIS HOSPITALIZATION WAS NOT LISTED IN THE OSHA FORM 170 DATA.)

Keywords: ELEC PROTECT EQUIP, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, LADDER, ELECTRICAL WORK, LOCKOUT, E C

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101216174 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.