Inspection Detail
Inspection: 101215887 - Maner'S & Sons Electrical Company, Inc.
Inspection Information - Office: Atlanta East Area Office
Site Address:
Maner'S & Sons Electrical Company, Inc.
1900 Auburn Avenue
Columbus, GA 31906
Mailing Address:
6926 Macon Road, Columbus, GA 31907
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/22/1988
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 03/25/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 901087486 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | 4 | |||
| Current Violations | 1 | 2 | 3 | |||
| Initial Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| Current Penalty | $1,000 | $0 | $0 | $0 | $0 | $1,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260020 B01 | 03/31/1988 | 05/02/1988 | $1,000 | $1,000 | $0 | 05/03/1988 | J - ALJ Decision | |
| 2. | 01001B | Serious | 19260021 B02 | 03/31/1988 | 05/02/1988 | $0 | $0 | $0 | 05/03/1988 | J - ALJ Decision | |
| 3. | 01002 | Serious | 19260416 A01 | 03/31/1988 | 04/03/1988 | $1,000 | $1,000 | $0 | 05/03/1988 | J - ALJ Decision | Citation has been deleted. |
| 4. | 02001 | Other | 19030002 A01 | 03/31/1988 | 04/03/1988 | $0 | $0 | $0 | 05/03/1988 | J - ALJ Decision | |
| 5. | 02002 | Other | 19260404 B01 II | 03/31/1988 | 04/03/1988 | $0 | $0 | $0 | 05/03/1988 | J - ALJ Decision |
Investigation Summary
DURING A CONSTRUCTION PROJECT TO REMODEL AN EXISTING BUILDING INTO A PHARMACY, AN EMPLOYEE WAS GOING TO ADD A CONDUIT TO AN EXISTING PANELBOARD WHILE IT REMAINED ENERGIZED. HE DRILLED INTO THE ENERGIZED PANELBOARD, AND THE DRILL CONTACTED LIVE PARTS. THE RESULTING FAULT TRIPPED THE MAIN CIRCUIT BREAKER, AND AT LEAST ONE OF THE THREE FUSES ON THE SERVICE POLE OPENED. ONE OR MORE OF THE THREE PHASE CONDUCTORS TO THE PANELBOARD REMAINED ENERGIZED. THE EMPLOYEE ATTEMPTED TO RESET THE MAIN CIRCUIT BREAKER, BUT COULD NOT DO SO. TWO OTHER EMPLOYEES REMOVED THE COVER FROM THE PANELBOARD AND, WITH ONLY A FLASHLIGHT TO PROVIDE ILLUMINATION, TRIED TO REPAIR THE MAIN CIRCUIT BREAKER. A FAULT OCCURRED, AND THE RESULTING ELECTRICAL EXPLOSION BURNED SIX EMPLOYEES. THREE OF THEM WERE HOSPITALIZED FOR THEIR INJURIES.
Keywords: BURN, CLOTHING, ELECTRICAL, PANELBOARD, ELECTRICAL WORK, LOCKOUT, E C, CIRCUIT BREAKER, ELECTRICAL FAULT, BLIND REACHING
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101215887 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
| 2 | 101215887 | Non Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |
Translate