Powered by GoogleTranslate

Inspection Detail

Inspection: 101199883 - Connecticut Light & Power Company

Inspection Information - Office: Hartford Area Office

 

Inspection Nr: 101199883
Report ID: 0112000
Date Opened: 08/22/1989

Site Address:
Connecticut Light & Power Company
49 Randoulf Roadad
Middletown, CT 06457

Mailing Address:
107 Selden Street, Berlin, CT 06037

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/12/1989

Emphasis:

Case Closed: 03/14/1990


Related Activity
Type Activity Nr Safety Health
Accident 360521199
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 3 3
Initial Penalty $6,000 $0 $0 $0 $0 $6,000
Current Penalty $2,400 $0 $0 $0 $0 $2,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 10/10/1989 10/13/1989 $800 $1,000 $0 I - Informal Settlement  
2. 01002A Serious 19260950 C01 10/10/1989 10/13/1989 $800 $1,000 $0 I - Informal Settlement  
3. 01002B Serious 19260950 C02 I 10/10/1989 10/13/1989 $0 $0 $0 I - Informal Settlement Citation has been deleted.
4. 01003 Serious 19260950 D01 IIA 10/10/1989 10/13/1989 $800 $1,000 $0 I - Informal Settlement  
5. 01004 Serious 19260954 D 10/10/1989 10/13/1989 $1,000 $1,000 $0 I - Informal Settlement Citation has been deleted.
6. 01005 Serious 19260954 E02 10/10/1989 10/13/1989 $1,000 $1,000 $0 I - Informal Settlement Citation has been deleted.
7. 01006 Serious 19260955 A06 10/10/1989 10/13/1989 $1,000 $1,000 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 816892
Event: 08/22/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A POWER LINE WORKER WAS WORKING FROM AN AERIAL LIFT, REMOVING PROTECTIVE GROUNDS. HE WAS HANDLING THE GROUNDS USING HIS RUBBER GLOVED HANDS. THE GROUNDS HAD BEEN PLACED FROM THE NEUTRAL OF THE SECONDARY CIRCUIT TO THE PRIMARY LINE CONDUCTORS. AS HE REMOVED THE ENDS OF THE PROTECTIVE GROUNDS FROM THE PRIMARY, HE PLACED THE LOOSE ENDS IN THE BUCKET OF THE AERIAL LIFT. AS HE WAS REPOSITIONING THE BUCKET TO REMOVE THE OTHER ENDS OF THE GROUNDS FROM THE NEUTRAL CONDUCTOR, HIS EAR CONTACTED THE PRIMARY CONDUCTOR. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, AERIAL LIFT, ELEC PROTECT EQUIP, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101199883 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close