Inspection Detail
Inspection: 101178820 - R.H. Bouligny
Inspection Information - Office: Charleston Area Office
Site Address:
R.H. Bouligny
Rt. 33, Philip Sporn Power Plant
New Haven, WV 25265
Mailing Address:
P.O. Box 5465, Charlotte, NC 28225
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/20/1993
Emphasis:
Case Closed: 12/01/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360503460 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 3 | 4 | |||
| Current Violations | 1 | 3 | 4 | |||
| Initial Penalty | $3,750 | $0 | $0 | $0 | $0 | $3,750 |
| Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260021 B02 | 10/06/1993 | 11/08/1993 | $2,000 | $3,750 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19260416 G08 | 10/06/1993 | 10/12/1993 | $0 | $0 | $0 | - | ||
| 3. | 02001 | Other | 19260059 E01 | 10/06/1993 | 10/12/1993 | $0 | $0 | $0 | - | ||
| 4. | 02002 | Other | 19260059 E01 II | 10/06/1993 | 10/19/1993 | $0 | $0 | $0 | - | ||
| 5. | 02003 | Other | 19261060 A01 V | 10/06/1993 | 10/19/1993 | $0 | $0 | $0 | - |
Investigation Summary
A power line crew was replacing the top circuit conductors on a double circuit overhead power line. They were replacing No. 2 AWG aluminum conductors with 4/0 conductors on the 12-kilovolt power line. The crew had replaced the conductors and was lowering the old conductors, which were deenergized, by rope, one section at a time. The crew foreman and an apprentice were at one pole with a rope connected to a deenergized conductor. A journeyman power line worker was at another pole, lowering the conductor to the ground. A fourth employee was on the ground, rolling up the slack conductor. This employee raised up and hit the conductor as it was hanging down. This knocked the conductor into the energized power line, and the employee on the ground was electrocuted.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101178820 | Fatality | Electric Shock | Electrical power installers and repairers |