Powered by GoogleTranslate

Inspection Detail

Inspection: 101130599 - Ponderosa Steakhouse Inc.

Inspection Information - Office: Chicago South Area Office

 

Inspection Nr: 101130599
Report ID: 0521700
Date Opened: 07/15/1988

Site Address:
Ponderosa Steakhouse Inc.
1335 Sibley Blvd.
Dolton, IL 60419

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5812

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/18/1988

Emphasis:

Case Closed: 04/13/1989


Related Activity
Type Activity Nr Safety Health
Accident 360421143
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $720 $0 $0 $0 $0 $720
Current Penalty $360 $0 $0 $0 $0 $360
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100304 F05 IVF 07/21/1988 07/24/1988 $360 $360 $0 08/11/1988 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19100305 G02 III 07/21/1988 07/24/1988 $360 $360 $0 08/11/1988 F - Formal Settlement  

Investigation Summary

Investigation Nr: 14212914
Event: 07/15/1988
ELECTRIC SHOCK - GROUND FAULT IN FOOD WARMER

An employee was filling a steam table with warm food. The strain relief on the food warmer's power supply cord was no longer working as intended. Consequently, the equipment grounding conductor and the grounded neutral conductor had pulled away from their screws in the cord's attachment plug. The equipment grounding conductor was apparently contacting the ungrounded circuit conductor, energizing the case of the food warmer. The employee filling the food warmer was electrocuted when he touched it.

Keywords: E GI V, ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, STRAIN RELIEF, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101130599 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.