Inspection Detail
Inspection: 101115483 - Nelson Division Of Nelson Industries
Inspection Information - Office: Madison Area Office
Site Address:
Nelson Division Of Nelson Industries
856 Fair St.
Mineral Point, WI 53565
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3714
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 08/21/1987
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 08/26/1987
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360117824 |
Investigation Summary
AN EMPLOYEE WAS ADJUSTING A WELDING GUN FOR A WIRE FEED OPERATION. THE WELDER WAS PLUGGED INTO A DEFECTIVE 480/277-VOLT, WALL-MOUNTED RECEPTACLE AT A POSITION 180 DEGREES OUT OF PROPER ALIGNMENT. THIS IMPROPER ALIGNMENT CAUSED THE EQUIPMENT GROUNDING CONDUCTOR TO BE CONNECTED TO ONE OF THE LINE CONDUCTORS, ENERGIZING THE FRAME OF THE WELDER. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: RECEPTACLE, ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, ELEC EQUIPMENT--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101115483 | Fatality | Electric Shock | Occupation not reported |
Translate