Inspection Detail
Inspection: 101081404 - Tri-State Contractors Inc.
Inspection Information - Office: Baton Rouge Area Office
Site Address:
Tri-State Contractors Inc.
5377 Highland Rd.
Baton Rouge, LA 70808
Mailing Address:
Po Box 762, Collierville, TN 38027
Union Status: NonUnion
SIC:1794
NAICS: 0
Inspection Type: Referral
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/17/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 11/23/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 900895624 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 5 | 8 | |||
| Current Violations | 3 | 5 | 8 | |||
| Initial Penalty | $840 | $0 | $0 | $0 | $0 | $840 |
| Current Penalty | $420 | $0 | $0 | $0 | $0 | $420 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260651 V | 03/16/1987 | 03/19/1987 | $140 | $280 | $0 | 03/30/1987 | R - Review Commission | |
| 2. | 01002 | Serious | 19260651 V | 03/16/1987 | 03/19/1987 | $140 | $280 | $0 | 03/30/1987 | R - Review Commission | |
| 3. | 01003 | Serious | 19100106 B03 IVA | 03/16/1987 | 03/19/1987 | $140 | $280 | $0 | 03/30/1987 | R - Review Commission | |
| 4. | 02001 | Other | 19260028 A | 03/16/1987 | 03/19/1987 | $0 | $0 | $0 | 03/30/1987 | R - Review Commission | |
| 5. | 02002 | Other | 19260102 A01 | 03/16/1987 | 03/19/1987 | $0 | $0 | $0 | 03/30/1987 | R - Review Commission | |
| 6. | 02003 | Other | 19260151 A03 | 03/16/1987 | 03/19/1987 | $0 | $0 | $0 | 03/30/1987 | R - Review Commission | |
| 7. | 02004 | Other | 19260350 H | 03/16/1987 | 03/19/1987 | $0 | $0 | $0 | 03/30/1987 | R - Review Commission | |
| 8. | 02005 | Other | 19260352 D | 03/16/1987 | 03/19/1987 | $0 | $0 | $0 | 03/30/1987 | R - Review Commission |
Investigation Summary
TWO EMPLOYEES WERE INSTALLING A SECONDARY VAPOR RECOVERY SYSTEM FOR A GASOLINE PUMP. THREE 12000-GALLON UNDERGROUND GASOLINE TANKS WERE BEING FILLED AT THE SAME TIME. THE VENTING SYSTEM FOR THE GASOLINE VAPORS HAD NOT BEEN COMPLETED BEFORE THE TANKS WERE FILLED. GASOLINE VAPORS WERE ALLOWED TO VENT FROM NINE DIFFERENT PLACES ON THE THREE TANKS WITHIN THE EXCAVATION FOR THE TANKS. THE VAPORS FROM THE TANKS HAD ACCUMULATED FOR ABOUT 4 HOURS. SOME NON-EXPLOSION-PROOF ELECTRIC TOOLS WERE BEING OPERATED AT THE EDGE OF THE EXCAVATION. THE TOOLS IGNITED THE VAPORS, AND A FLASH FIRE RESULTED, SEVERELY BURNING THE TWO EMPLOYEES. BOTH WERE HOSPITALIZED FOR THEIR INJURIES.
Keywords: BURN, CLOTHING, EXCAVATION, ELECTRICAL, E C, EXPLOSION, GASOLINE, EQUIPMENT APPROVAL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 101081404 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
| 2 | 101081404 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |