Powered by GoogleTranslate

Inspection Detail

Inspection: 101076735 - H. O. Mohr & Associates

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 101076735
Report ID: 0626600
Date Opened: 04/30/1986

Site Address:
H. O. Mohr & Associates
5540 Broom Street
Houston, TX 77091

Mailing Address:
2707 N. Loop West, Suite 200, Houston, TX 77008

Union Status: NonUnion

SIC:8711

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/06/1986

Emphasis:

Case Closed: 06/03/1986


Related Activity
Type Activity Nr Safety Health
Accident 360706733
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 2 3
Initial Penalty $300 $0 $0 $0 $0 $300
Current Penalty $150 $0 $0 $0 $0 $150
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100304 F05 05/19/1986 05/23/1986 $150 $300 $0 I - Informal Settlement  
2. 02001 Other 19030002 A01 05/19/1986 05/22/1986 $0 $0 $0 -  
3. 02002 Other 19040002 A 05/19/1986 05/27/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14498679
Event: 04/29/1986
ELECTRIC SHOCK - GROUND FAULT IN INDUCTION HEATER

AN EMPLOYEE WAS WORKING IN AN ENGINEERING FIRM'S TEST LAB. HE WAS SETTING UP A 480-VOLT INDUCTION HEATER (PALMER INDUSTRIAL HEATING EQUIPMENT, MODEL NUMBER 5543, SERIAL NUMBER C43) TO HEAT SOME BEARINGS. HE WAS HOLDING A METAL THERMOCOUPLE PROBE IN ONE HAND. HE THEN GROUNDED HIMSELF THROUGH EITHER THE METAL CORD GRIP ON A 120-VOLT FLEXIBLE CORD OR THE METAL THERMOCOUPLE READOUT BOX. THE THERMOCOUPLE WAS LYING ON TOP OF THE INDUCTION HEATER. BECAUSE THE GROUNDING CONDUCTOR FOR THE HEATER WAS MISWIRED IN THE THREE-PHASE PLUG TO ONE OF THE CIRCUIT CONDUCTORS, THE FRAME OF THE HEATER WAS ENERGIZED AT 277 VOLTS TO GROUND. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 101076735 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.