Inspection Detail
Inspection: 100869312 - American Incapsallation & Installation, Inc.
Inspection Information - Office: Parsippany Area Office
Site Address:
American Incapsallation & Installation, Inc.
1599 Littleton Road
Parsippany, NJ 07054
Mailing Address:
529 Doe Lane, Cherry Hill, NJ 08034
Union Status: NonUnion
SIC:1799
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/15/1987
Emphasis:
Case Closed: 12/08/1987
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360663587 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 1 | 3 | |||
| Current Violations | 2 | 1 | 3 | |||
| Initial Penalty | $990 | $0 | $0 | $0 | $0 | $990 |
| Current Penalty | $990 | $0 | $0 | $0 | $0 | $990 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260404 B01 I | 10/19/1987 | 10/22/1987 | $350 | $350 | $0 | - | ||
| 2. | 01001B | Serious | 19260404 F07 IVC | 10/19/1987 | 10/22/1987 | $0 | $0 | $0 | - | ||
| 3. | 01002 | Serious | 19260416 A01 | 10/19/1987 | 10/22/1987 | $640 | $640 | $0 | - | ||
| 4. | 02001 | Other | 19260451 E08 | 10/19/1987 | 10/22/1987 | $0 | $0 | $0 | - |
Investigation Summary
A CONSTRUCTION LABORER WAS REPLACING FLUORESCENT LIGHTS AT A CONSTRUCTION JOBSITE THAT HAD JUST COMPLETED ASBESTOS REMOVAL. UPON CHANGING SEVERAL BULBS, HE SAW THAT TWO FIXTURES WERE STILL NOT WORKING. HE OPENED THE JUNCTION BOX FOR THE FIRST FIXTURE AND RECONNECTED THE CONDUCTORS. THIS LIGHT CAME ON. HE THEN OPENED THE JUNCTION BOX FOR THE SECOND FIXTURE AND STARTED TO RECONNECT ITS CONDUCTORS. DURING THIS OPERATION, HE CONTACTED ONE OF THE ENERGIZED 277-VOLT CONDUCTORS AND WAS ELECTROCUTED. THE PANELBOARD FOR THE LIGHTING INSTALLATION WAS PLAINLY LABELED, BUT THE LIGHTING CIRCUIT HAD NOT BEEN DEENERGIZED BEFORE THE EMPLOYEE ATTEMPTED THE REPAIR.
Keywords: ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 100869312 | Fatality | Electric Shock | Construction laborers |