Powered by GoogleTranslate

Inspection Detail

Inspection: 100858638 - Lincoln Electrical Contracting Corp.

Inspection Information - Office: Concord Area Office

 

Inspection Nr: 100858638
Report ID: 0111700
Date Opened: 06/01/1989

Site Address:
Lincoln Electrical Contracting Corp.
1 Fine Chocolate Place
Stratham, NH 03885

Mailing Address:
395 Main St., Salem, NH 03079

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/20/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 05/11/1990


Related Activity
Type Activity Nr Safety Health
Accident 360516256
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 2 3 5
Initial Penalty $1,450 $0 $0 $0 $0 $1,450
Current Penalty $900 $0 $0 $0 $0 $900
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260020 B01 06/26/1989 06/29/1989 $500 $810 $0 I - Informal Settlement  
2. 01002 Serious 19260417 B 06/26/1989 06/29/1989 $400 $640 $0 I - Informal Settlement  
3. 02001 Other 19260059 E01 06/26/1989 07/21/1989 $0 $0 $0 -  
4. 02002 Other 19260059 G01 06/26/1989 07/21/1989 $0 $0 $0 -  
5. 02003 Other 19260059 H 06/26/1989 07/21/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14530133
Event: 05/31/1989
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

TWO ELECTRICIANS AND THEIR FOREMAN WERE TROUBLESHOOTING A 277-VOLT EMERGENCY LIGHTING CIRCUIT. THE TWO ELECTRICIANS WERE DISCONNECTING THE FAULTY CIRCUIT AT TWO JUNCTION BOXES LOCATED ABOVE A CEILING. THEY HAD ASSUMED THAT THE CIRCUIT BREAKER FOR THE CIRCUIT WAS OFF. ONE OF THE ELECTRICIANS HAD TESTED FOR POWER AT ONE OF THE JUNCTION BOXES AND FOUND THE CIRCUIT TO BE DEENERGIZED. THE FOREMAN WAS IN THE ELECTRICAL ROOM TROUBLESHOOTING THE SAME CIRCUIT AND WAS TURNING THE CIRCUIT BREAKER OFF AND ON. THE ELECTRICIAN WHO HAD TESTED THE CIRCUIT RECEIVED AN ELECTRIC SHOCK (HE WAS NOT LIST AS BEING INJURED) AND, MOMENTS LATER, HEARD THE OTHER ELECTRICIAN YELL. A THIRD ELECTRICIAN WENT INTO THE CEILING AFTER HEARING THE SAME YELL AND FOUND THE SECOND ELECTRICIAN LYING ON THE JUNCTION BOX, CONVULSING. THE CIRCUIT WAS DEENERGIZED AND CARDIO-PULMONARY RESUSCITATION WAS BEGUN IN THE CEILING AREA. IN SPITE OF THESE RESCUE EFFORTS, THE EMPLOYEE DIED.

Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100858638 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close