Inspection: 100751783 - Turbo Electrical Contractors, Inc.

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 100751783
Report ID: 0626600
Date Opened: 11/09/1992

Site Address:
Turbo Electrical Contractors, Inc.
10000 Old Katy Rd., Suite 275
Houston, TX 77055

Mailing Address:
13419 Emmett Rd., Houston, TX 77041

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/12/1992

Emphasis:

Case Closed: 04/12/1993


Related Activity
Type Activity Nr Safety Health
Accident 360900757
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $750 $0 $750
Current Penalty $0 $0 $0 $375 $0 $375
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19040008 12/11/1992 12/16/1992 $375 $750 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14398481
Event: 10/28/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN ELECTRICIAN WAS STANDING ON THE FOURTH RUNG OF A 6-FOOT FIBERGLASS STEPLADDER, TROUBLESHOOTING CONDUCTORS IN A JUNCTION BOX LOCATED ABOVE CEILING TILE. THE EMPLOYEE WAS USING AN IDEAL VOL-CON TESTER (MODEL NO. 61076) TO TRACE CONDUCTORS TO PANELS. HE WAS TO DETERMINE WHETHER OR NOT THE CONDUCTORS WOULD BE NEEDED AND TO TERMINATE THE CONDUIT AND CONDUCTORS NOT NEEDED IN AN EMPTY LEASED SPACE. THE ELECTRICIAN, WHO WAS APPARENTLY TOUCHING A WATER PIPE LOCATED ABOUT 18 INCHES BELOW AND 4 INCHES TO ONE SIDE OF THE JUNCTION BOX, CONTACTED A 207-VOLT CONDUCTOR WITH HIS RIGHT INDEX FINGER AND RECEIVED AN ELECTRIC SHOCK. THE ELECTRICIAN FELL, AND A COWORKER STANDING NEXT TO THE LADDER GRABBED HIM BY THE WAIST AND EASED HIM TO THE FLOOR. THE COWORKER RAN TO THEIR TRUCK AND CALLED HIS OFFICE TO DISPATCH AN AMBULANCE. THE ELECTRICIAN DIED AT THE HOSPITAL ABOUT AN HOUR AFTER THE ACCIDENT. HE HAD BEEN ELECTROCUTED.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICAL TESTING, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, WATER PIPE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100751783 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.