Powered by GoogleTranslate

Inspection Detail

Inspection: 100739184 - L.W.K. Electrical Co., Inc.

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 100739184
Report ID: 0626600
Date Opened: 05/22/1987

Site Address:
L.W.K. Electrical Co., Inc.
2020 Gault Rd.
Houston, TX 77039

Mailing Address:
P.O. Box 87865, Houston, TX 77287

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/26/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/03/1988


Related Activity
Type Activity Nr Safety Health
Accident 360345078
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 2 9
Current Violations 5 2 7
Initial Penalty $3,160 $0 $0 $0 $0 $3,160
Current Penalty $1,520 $0 $0 $0 $0 $1,520
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260020 B02 06/25/1987 06/30/1987 $320 $640 $0 I - Informal Settlement  
2. 01001B Serious 19260020 B02 06/25/1987 06/30/1987 $0 $0 $0 I - Informal Settlement Citation has been deleted.
3. 01002 Serious 19260550 A05 06/25/1987 07/15/1987 $320 $640 $0 I - Informal Settlement  
4. 01003A Serious 19260550 A06 06/25/1987 07/16/1987 $175 $350 $0 I - Informal Settlement  
5. 01003B Serious 19260550 A06 06/25/1987 06/30/1987 $0 $0 $0 -  
6. 01004 Serious 19260550 A07 II 06/25/1987 06/30/1987 $250 $250 $0 I - Informal Settlement Citation has been deleted.
7. 01005A Serious 19260955 A05 I 06/25/1987 06/30/1987 $175 $0 $0 I - Informal Settlement  
8. 01005B Serious 19260955 A06 I 06/25/1987 06/30/1987 $0 $0 $0 I - Informal Settlement  
9. 01006 Serious 19260955 A06 I 06/25/1987 06/30/1987 $530 $640 $0 I - Informal Settlement  
10. 01007 Serious 19260955 A06 II 06/25/1987 06/30/1987 $640 $640 $0 I - Informal Settlement Citation has been deleted.
11. 02001 Other 19030002 A01 06/25/1987 06/28/1987 $0 $0 $0 -  
12. 02002 Other 19260550 A04 06/25/1987 06/30/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14412498
Event: 05/21/1987
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU POLE GROUND

A power line crew was setting utility poles. The crew was using an electric line truck with a boom to hoist a replacement pole next to an existing pole. The employees were setting the new pole between two phase conductors of a three-phase, 7200-volt-to-ground overhead power line. The employees had put rubber insulating line hose on the middle phase conductor and had installed a No. 4 solid copper ground wire on the pole. As the line truck was positioning the pole between the phase conductors, the ground wire on the pole contacted an uninsulated portion of the overhead line. One of the employees on the crew was apparently getting a drink of water by the truck. The employee, who had one hand on the truck when the contact occurred, was electrocuted.

Keywords: BOOM TRUCK, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100739184 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.