Inspection Detail
Inspection: 100702364 - Dean Electric, Inc.
Inspection Information - Office: Dallas Area Office
Site Address:
Dean Electric, Inc.
1300 Honor Drive
Desoto, TX 75115
Mailing Address:
1038c South Cedar Hill Road, Cedar Hill, TX 75104
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 06/18/1987
Emphasis:
Case Closed: 11/30/1987
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360137855 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $420 | $0 | $0 | $0 | $0 | $420 |
Current Penalty | $420 | $0 | $0 | $0 | $0 | $420 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260021 B02 | 07/15/1987 | 07/22/1987 | $420 | $420 | $0 | - | ||
2. | 01001B | Serious | 19260416 A03 | 07/15/1987 | 07/22/1987 | $0 | $0 | $0 | - | ||
3. | 01001C | Serious | 19260417 A | 07/15/1987 | 07/22/1987 | $0 | $0 | $0 | - |
Investigation Summary
Two electricians were at the base of some steel poles, working on two overhead lights. One of the poles contained all of the conductors for both lights in its base. The light on a second pole, which was not working, was fed from the first pole through an underground conduit. The two employees had opened the circuit breaker and tested conductors in the first pole to make sure they were deenergized. The employees had removed the old conductors from the conduit feeding the light on the second pole. They inserted a metal fish tape in the empty conduit between the two poles. It then began raining, so they went to lunch. When they returned, it was still raining. Consequently, they decided to remove the fish tape and leave the site. One employee grabbed the fish tape while standing on concrete and took two steps backwards into the grass. The fish tape was energized, and the employee was electrocuted.
Keywords: LIGHTING CIRCUIT, METAL WIRE, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 100702364 | Fatality | Electric Shock | Electricians |