Powered by GoogleTranslate

Inspection Detail

Inspection: 100694868 - Long Island Lighting Co., Inc.

Inspection Information - Office: Long Island Area Office

 

Inspection Nr: 100694868
Report ID: 0214700
Date Opened: 12/01/1987

Site Address:
Long Island Lighting Co., Inc.
Barrister Lane & Scooter Lane
Levittown, NY 11756

Mailing Address:
175 E. Old Country Road, Hicksville, NY 11801

Union Status: Union

SIC:4931

NAICS: 0 


Inspection Type: Referral

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/11/1987

Emphasis:

Case Closed: 02/04/1988


Related Activity
Type Activity Nr Safety Health
Referral 900838277 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $810 $0 $0 $0 $0 $810
Current Penalty $810 $0 $0 $0 $0 $810
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B01 12/30/1987 01/03/1988 $810 $810 $0 -  

Investigation Summary

Investigation Nr: 14562466
Event: 12/01/1987
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

AN APPRENTICE LINEMAN OF 6 MONTHS WAS ASSIGNED BY HIS FOREMAN TO CLIMB A UTILITY POLE TO DISCONNECT A SECONDARY DEENERGIZED 240-VOLT LINE. HIS FACE BRUSHED AGAINST THE CLAMP OF A LINE HANGING LOOSE FROM ABOVE WHEN HE WAS TAPING A WIRE. HIS HAND HAD ALSO MADE CONTACT. THERE WAS A FLASH, AND THE EMPLOYEE SLID DOWN TO THE CABLE TELEVISION LINE, BURNED AND UNCONSCIOUS. HE WAS HOSPITALIZED, AND HIS EXTENSIVELY BURNED LEFT ARM WAS AMPUTATED TO THE ELBOW. HE REQIRED FACIAL PLASTIC SURGERY. INVESTIGATION DETERMINED THAT BOTH THE FOREMAN AND FIRST CLASS LINEMAN HAD FAILED TO NOTE THAT THERE WAS A HANGING LINE. THIS LINE TRAVELED TO AN INSULATOR ON THE UPPER POLE ARM AND CONTINUED TO A LOADSIDE TAP, THEN TO A FUSE HOLDER IN THE CLOSED POSITION, THEN ON TO A LINESIDE TAP CONNECTED TO AN ENERGIZED 7620-VOLT LINE. THE ROUTE THE LINE FOLLOWED WAS OBVIOUS FROM GROUND LEVEL TO THE PERSONNEL.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100694868 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.