Inspection Detail
Inspection: 100694868 - Long Island Lighting Co., Inc.
Inspection Information - Office: Long Island Area Office
Site Address:
Long Island Lighting Co., Inc.
Barrister Lane & Scooter Lane
Levittown, NY 11756
Mailing Address:
175 E. Old Country Road, Hicksville, NY 11801
Union Status: Union
SIC:4931
NAICS: 0
Inspection Type: Referral
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/11/1987
Emphasis:
Case Closed: 02/04/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 900838277 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $810 | $0 | $0 | $0 | $0 | $810 |
| Current Penalty | $810 | $0 | $0 | $0 | $0 | $810 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260950 B01 | 12/30/1987 | 01/03/1988 | $810 | $810 | $0 | - |
Investigation Summary
AN APPRENTICE LINEMAN OF 6 MONTHS WAS ASSIGNED BY HIS FOREMAN TO CLIMB A UTILITY POLE TO DISCONNECT A SECONDARY DEENERGIZED 240-VOLT LINE. HIS FACE BRUSHED AGAINST THE CLAMP OF A LINE HANGING LOOSE FROM ABOVE WHEN HE WAS TAPING A WIRE. HIS HAND HAD ALSO MADE CONTACT. THERE WAS A FLASH, AND THE EMPLOYEE SLID DOWN TO THE CABLE TELEVISION LINE, BURNED AND UNCONSCIOUS. HE WAS HOSPITALIZED, AND HIS EXTENSIVELY BURNED LEFT ARM WAS AMPUTATED TO THE ELBOW. HE REQIRED FACIAL PLASTIC SURGERY. INVESTIGATION DETERMINED THAT BOTH THE FOREMAN AND FIRST CLASS LINEMAN HAD FAILED TO NOTE THAT THERE WAS A HANGING LINE. THIS LINE TRAVELED TO AN INSULATOR ON THE UPPER POLE ARM AND CONTINUED TO A LOADSIDE TAP, THEN TO A FUSE HOLDER IN THE CLOSED POSITION, THEN ON TO A LINESIDE TAP CONNECTED TO AN ENERGIZED 7620-VOLT LINE. THE ROUTE THE LINE FOLLOWED WAS OBVIOUS FROM GROUND LEVEL TO THE PERSONNEL.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 100694868 | Hospitalized injury | Electric Shock | Occupation not reported |
Translate