Inspection Detail
Inspection: 100657725 - J & J Insulation And Acoustics, Inc.
Inspection Information - Office: Corpus Christi Area Office
Site Address:
J & J Insulation And Acoustics, Inc.
1 Battlin Buc Blvd.
Corpus Christi, TX 78408
Mailing Address:
660 Cantwell, Corpus Christi, TX 78408
Union Status: NonUnion
SIC:1742
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/22/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 04/25/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360158943 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 4 | 7 | |||
Current Violations | 3 | 4 | 7 | |||
Initial Penalty | $1,540 | $0 | $0 | $0 | $0 | $1,540 |
Current Penalty | $770 | $0 | $0 | $0 | $0 | $770 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260404 F06 | 07/24/1987 | 07/27/1987 | $280 | $560 | $0 | 08/14/1987 | F - Formal Settlement | |
2. | 01002 | Serious | 19260404 F07 IVC | 07/24/1987 | 07/27/1987 | $245 | $490 | $0 | 08/14/1987 | F - Formal Settlement | |
3. | 01003 | Serious | 19260405 A02 IIG | 07/24/1987 | 07/27/1987 | $245 | $490 | $0 | 08/14/1987 | F - Formal Settlement | |
4. | 02001 | Other | 19260403 G | 07/24/1987 | 07/27/1987 | $0 | $0 | $0 | 08/14/1987 | F - Formal Settlement | |
5. | 02002 | Other | 19260404 B01 I | 07/24/1987 | 07/27/1987 | $0 | $0 | $0 | 08/14/1987 | F - Formal Settlement | |
6. | 02003 | Other | 19260405 A02 IIJ | 07/24/1987 | 07/27/1987 | $0 | $0 | $0 | 08/14/1987 | F - Formal Settlement | |
7. | 02004 | Other | 19260432 A01 I | 07/24/1987 | 07/27/1987 | $0 | $0 | $0 | 08/14/1987 | F - Formal Settlement |
Investigation Summary
Three employees were beneath the floor of a gymnasium, cleaning and encapsulating metal pipes from which asbestos had been removed. One of the employees was using a 120-volt portable electric lamp that was not grounded. No ground-fault circuit interrupter was protecting the circuit, and neither the lamp nor the extension cord set was approved for use in wet locations. Apparently, a ground fault energized the metal part of the portable lamp. The employee using the lamp was electrocuted.
Keywords: E GI V, ELECTRICAL, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC LIGHT--PORT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 100657725 | Fatality | Electric Shock | Occupation not reported |