Inspection Detail
Inspection: 100652122 - Island Construction Inc.
Inspection Information - Office: Corpus Christi Area Office
Site Address:
Island Construction Inc.
Hwy. 361, Ferry Landing
Port Aransas, TX 78373
Mailing Address:
P.O. Box 189, Port Aransas, TX 78373
Union Status: NonUnion
SIC:1799
NAICS: 0
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/03/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 05/31/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360158976 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 4 | 5 | |||
| Current Violations | 1 | 4 | 5 | |||
| Initial Penalty | $210 | $0 | $0 | $0 | $0 | $210 |
| Current Penalty | $210 | $0 | $0 | $0 | $0 | $210 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260550 A15 I | 08/06/1987 | 08/10/1987 | $210 | $210 | $0 | 08/27/1987 | F - Formal Settlement | |
| 2. | 02001 | Other | 19260550 A05 | 08/06/1987 | 08/20/1987 | $0 | $0 | $0 | 08/27/1987 | F - Formal Settlement | |
| 3. | 02002 | Other | 19260550 A06 | 08/06/1987 | 08/20/1987 | $0 | $0 | $0 | 08/27/1987 | F - Formal Settlement | |
| 4. | 02003 | Other | 19260550 A14 I | 08/06/1987 | 08/12/1987 | $0 | $0 | $0 | 08/27/1987 | F - Formal Settlement | |
| 5. | 02004 | Other | 19260550 A17 | 08/06/1987 | 08/20/1987 | $0 | $0 | $0 | 08/27/1987 | F - Formal Settlement |
Investigation Summary
Two employees were removing a lighting pole. The pole had two arms with a lighting fixture on each arm. The pole was 12.8 meters (42 feet) high and 6.4 meters (21 feet) away from a 7200-volt overhead power line. The power line was located 8.8 meters (29 feet) above the ground. A crane raised the pole so that it could clear its mounting bolts and then moved the pole until it was about 4.6 meters (15 feet) away from the power lines before lowering it. One of the employees was standing on the base of the pole as it was being lowered. The other employee was standing about 0.6 meters (2 feet) from the pole as the top of the light contacted the overhead line. This employee received an electric shock and fell onto his right side, contacting the energized pole. He was electrocuted. The employee at the base of the pole jumped free of the pole. However, he also received an electric shock and sustained burns to his hand as he tried to pull his coworker from the pole.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, E GI IA, ELECTRIC SHOCK, BURN, ELECTROCUTED, LOAD LINE, CRANE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 100652122 | Occupation Not Listed |
Translate