Powered by GoogleTranslate

Inspection Detail

Inspection: 100435650 - New England Power Company

Inspection Information - Office: Boston South Area Office

 

Inspection Nr: 100435650
Report ID: 0111400
Date Opened: 11/25/1986

Site Address:
New England Power Company
24 Fort Avenue
Salem, MA 01970

Mailing Address:
, , 00000

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/06/1987

Emphasis:

Case Closed: 04/20/1987


Related Activity
Type Activity Nr Safety Health
Accident 360669360
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $480 $0 $0 $0 $0 $480
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 03/13/1987 03/16/1987 $480 $480 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 656801
Event: 11/21/1986
ELECTRIC SHOCK - GROUND FAULT IN RECEPTACLE OUTLET

AN AUDIOMETRIC TESTING TRAILER WAS WITHOUT ELECTRIC POWER EVEN THOUGH THE TRAILER'S SUPPLY CORD WAS PLUGGED INTO A 480-VOLT RECEPTACLE OUTLET. (IT WAS RAINING HEAVILY AT THE TIME.) AN ELECTRICIAN, WHO WAS CHECKING ON THE PROBLEM, WENT TO SEE IF THE MAIN DISCONNECT FOR THE OUTLET WAS OPEN. WHILE THE ELECTRICIAN WAS GONE, AN AUDIOMETRIC TESTING TECHNICIAN REACHED INTO THE REEL COMPARTMENT OF THE TRAILER AND WAS ELECTROCUTED WHEN HE TOUCHED THE TRAILER FRAME. HE WAS STANDING ON A METAL TRENCH COVER AT THE TIME. FURTHER INVESTIGATION REVEALED THAT THE EQUIPMENT GROUNDING CONDUCTOR FOR THE RECEPTACLE HAD BEEN CONNECTED TO ONE OF THE CIRCUIT TERMINALS AND THAT THE CORRESPONDING CIRCUIT CONDUCTOR HAD BEEN CONNECTED TO THE EQUIPMENT GROUNDING TERMINAL. THIS CAUSED VOLTAGE TO BE IMPRESSED ON THE TRAILER FRAME, AND A VOLTAGE TEST INDICATED THAT THERE WAS 250 VOLTS BETWEEN THE TRAILER AND THE METAL TRENCH COVER. CARDIOPULMONARY RESUSCITATION WAS ATTEMPTED ON THE TECHNICIAN WITHOUT SUCCESS. THE AMOUNT OF TIME THAT HAD ELAPSED BETWEEN CONTACT AND CPR APPLICATION WAS NOT REPORTED.

Keywords: RECEPTACLE, ELECTRICAL, CPR, E GI VII, GROUND FAULT, ELECTROCUTED, TRAILER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100435650 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.