Powered by GoogleTranslate

Inspection Detail

Inspection: 100381276 - Montgomery Elevator Company

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 100381276
Report ID: 0420600
Date Opened: 11/26/1985

Site Address:
Montgomery Elevator Company
Cape Canaveral Air Force Station, Bldg 27200
Cape Canaveral, FL 32207

Mailing Address:
4836 Victor Street, Jacksonville, FL 32207

Union Status: Union

SIC:1796

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/26/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/18/1986


Related Activity
Type Activity Nr Safety Health
Accident 360710727
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260400 H01 01/24/1986 01/24/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14346530
Event: 11/19/1985
ELECTRIC SHOCK - GROUND FAULT IN ELEVATOR CIRCUIT

AN EMPLOYEE WAS INSTALLING WIRING FOR AN ELEVATOR CAR. AN ELECTRICAL FAULT OCCURRED IN ONE OF THE CIRCUITS AT AN OVERHEAD LIGHT INSIDE THE ELEVATOR CAR, ENERGIZING THE CAR ITSELF AT 120 VOLTS. IN WIRING THE CIRCUIT AT THE PANELBOARD, THE EMPLOYEE HAD NOT CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR FOR THE ELEVATOR. THEREFORE, THE 10-AMPERE FUSE PROTECTING THE CIRCUIT DID NOT DETECT THE FAULT, AND THE CAR REMAINED ENERGIZED. THE EMPLOYEE REACHED INSIDE THE ELEVATOR SHAFT TO RETRIEVE A 10-FOOT PIECE OF METAL CONDUIT WITH HIS LEFT HAND, WHILE HIS RIGHT HAND WAS ON THE CAR. THE CONDUIT WAS STANDING VERTICALLY ON THE ELEVATOR PIT FLOOR, PROVIDING A PATH TO GROUND. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELEVATOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100381276 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.