Inspection Detail
Inspection: 100363340 - Guardian Chemical Company
Inspection Information - Office: Atlanta East Area Office
Site Address:
Guardian Chemical Company
694 Jefferson Street N.W.
Atlanta, GA 30318
Mailing Address:
P. O. Box 93667, Atlanta, GA 30377
Union Status: NonUnion
SIC:2842
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/18/1986
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 02/18/1987
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 900692419 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 2 | 3 | |||
Current Violations | 1 | 2 | 3 | |||
Initial Penalty | $200 | $0 | $0 | $0 | $0 | $200 |
Current Penalty | $200 | $0 | $0 | $0 | $0 | $200 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100106 B02 VA | 06/23/1986 | 09/15/1986 | $200 | $200 | $0 | P - Petition to Mod Abatement | ||
2. | 01001B | Serious | 19100106 B02 IIA | 06/23/1986 | 07/25/1986 | $0 | $0 | $0 | - | ||
3. | 01001C | Serious | 19100106 B06 | 06/23/1986 | 07/25/1986 | $0 | $0 | $0 | - | ||
4. | 01001D | Serious | 19100106 B07 I | 06/23/1986 | 09/15/1986 | $0 | $0 | $0 | P - Petition to Mod Abatement | ||
5. | 01001E | Serious | 19101200 F04 | 06/23/1986 | 07/25/1986 | $0 | $0 | $0 | - | ||
6. | 02001 | Other | 19101200 E01 | 06/23/1986 | 07/25/1986 | $0 | $0 | $0 | - | ||
7. | 02002 | Other | 19101200 G02 | 06/23/1986 | 09/15/1986 | $0 | $0 | $0 | P - Petition to Mod Abatement |
Investigation Summary
EMPLOYEE #1 IS AN EMPLOYEE OF A CHEMICAL WHOLESALE DISTRIBUTION COMPANY. HE WAS DELIVERING APPROXIMATELY 1,000 GALLONS OF SHELL SOL 340 (MINERAL SPIRITS) TO A CHEMICAL MANUFACTURING COMPANY. HE CONNECTED THE HOSE FROM HIS TRUCK TO THE INLET VALVE OF THE 1,000 GALLON STORAGE TANK AND BEGAN PUMPING THE SOLVENT INTO THE TANK. AFTER A FEW MINUTES THE HOSE SUDDENLY RUPTURED AND THE END OF THE CYLINDRICAL, HORZONTAL STEEL STORAGE TANK BLEW OUT. THE EMPLOYEE'S BACK WAS TURNED WHEN THE RUPTURE OCCURRED. HE WAS SOAKED WITH THE LIQUID. NO FIRE OCCURRED. THE STORAGE TANK'S RELIEF VALVE WAS AN OPW 95-UT 2 INCH PRESSURE-VACUUM RELIEF VALVE. THE VALVE WAS ABOUT 20 YEARS OLD. THE TANK WAS APPROXIMATELY 25 YEARS OLD. IT APPEARS THAT THE RELIEF VALVE OPENED ONLY PARTIALLY. 500 TO 600 GALLONS OF SOLVENT WERE PUMPED INTO THE TANK BEFORE THE EXCESSIVE PRESSURE CAUSED THE BLOW OUT. EMPLOYEE #1 RECEIVED FIRST DEGREE BURNS ON HIS BACK.
Keywords: VALVE, CHEMICAL BURN, TANK, HOSE, RUPTURE, BACK, HIGH PRESSURE, SKIN, CHEMICAL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 100363340 | Occupation Not Listed |