Powered by GoogleTranslate

Inspection Detail

Inspection: 100338573 - Bekaert Steel Wire Corp.

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 100338573
Report ID: 0418100
Date Opened: 10/23/1985

Site Address:
Bekaert Steel Wire Corp.
Darlington Drive
Rome, GA 30161

Mailing Address:
P. O. Box G, Rome, GA 30161

Union Status: Union

SIC:3496

NAICS: 0 


Inspection Type: Complaint

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/30/1985

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 12/06/1985


Related Activity
Type Activity Nr Safety Health
Complaint 71538722 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 6 7
Current Violations 1 6 7
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $480 $0 $0 $0 $0 $480
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 H03 II 11/15/1985 11/18/1985 $480 $480 $0 -  
2. 02001 Other 19100037 Q01 11/15/1985 11/26/1985 $0 $0 $0 -  
3. 02002 Other 19100179 B05 11/15/1985 11/26/1985 $0 $0 $0 -  
4. 02003 Other 19100179 G01 V 11/15/1985 11/26/1985 $0 $0 $0 -  
5. 02004 Other 19100252 A02 IID 11/15/1985 11/26/1985 $0 $0 $0 -  
6. 02005 Other 19100304 F05 V 11/15/1985 11/26/1985 $0 $0 $0 -  
7. 02006 Other 19100305 G01 III 11/15/1985 11/26/1985 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14332498
Event: 10/22/1985
ELECTRIC SHOCK AND BURNS - VOLTAGE BACKFEED IN SUBSTATION

THREE EMPLOYEES WERE CLEANING THE MAIN LUGS IN SUBSTATION 11 IN PREPARATION FOR THE TYING IN OF A FEEDER TO SUBSTATION 12. THE MAIN POWER SWITCH TO THESE TWO SUBSTATIONS AND TO SUBSTATIONS 13 AND 14 HAD BEEN OPENED AND LOCKED OUT. HOWEVER, IN ORDER TO MAINTAIN POWER TO A PLANT AIR COMPRESSOR, A CIRCUIT BREAKER IN SUBSTATION 14 WAS TO BE PROVIDED WITH TEMPORARY POWER FROM ANOTHER SUBSTATION. THIS CIRCUIT BREAKER WAS SUPPOSED TO BE OPEN TO PREVENT BACKFEED TO THE FOUR DEENERGIZED SUBSTATIONS. THE SUPERVISOR FOR THESE EMPLOYEES CHECKED THE CIRCUIT BREAKER AND FOUND IT TO BE OPEN. UNFORTUNATELY, HE HAD MISREAD THE INDICATOR DUE TO INADEQUATE ILLUMINATION. WHEN THE TEMPORARY POWER SUPPLY WAS CONNECTED, A VOLTAGE BACKFEED OF 13 KILOVOLTS ENERGIZED THE LUGS ON WHICH THE EMPLOYEES WERE WORKING, SHOCKING AND BURNING ALL THREE EMPLOYEES. TWO OF THEM WERE HOSPITALIZED WITH SECOND DEGREE BURNS TO THEIR LEFT HANDS AND ARMS. THE OTHER EMPLOYEE RECEIVED FIRST DEGREE BURNS TO HIS LEFT HAND.

Keywords: BURN, CLOTHING, VOLTAGE BACKFEED, ELECTRICAL, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100338573 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 100338573 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
3 100338573 Non Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.