Inspection Detail
Inspection: 1003042.015 - Duke Energy Florida, Inc.
Inspection Information - Office: Jacksonville Area Office
Site Address:
Duke Energy Florida, Inc.
4940 Cr 316
Reddick, FL 32686
Mailing Address:
550 S. Tyron Street, Charlotte, NC 28202
Union Status: Union
SIC:
NAICS: 221121/Electric Bulk Power Transmission and Control
Inspection Type: Fat/Cat
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/23/2014
Emphasis:
Case Closed: 10/15/2015
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 916754 | ||
Referral | 915487 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 4 | 1 | 1 | 6 | ||
Current Violations | 5 | 1 | 6 | |||
Initial Penalty | $20,000 | $70,000 | $0 | $0 | $0 | $90,000 |
Current Penalty | $35,000 | $0 | $0 | $0 | $0 | $35,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100022 A01 | 04/10/2015 | $7,000 | $3,000 | $0 | I - Informal Settlement | |||
2. | 01002 | Serious | 19100269 O02 II | 04/10/2015 | 11/30/2015 | $7,000 | $7,000 | $0 | I - Informal Settlement | ||
3. | 01003 | Serious | 19100269 O04 V | 04/10/2015 | 08/31/2015 | $7,000 | $3,000 | $0 | I - Informal Settlement | ||
4. | 01004 | Serious | 19100269 O06 II | 04/10/2015 | 11/30/2015 | $7,000 | $7,000 | $0 | I - Informal Settlement | ||
5. | 01005 | Serious | 19100269 O05 IV | 04/10/2015 | 11/30/2015 | $7,000 | $70,000 | $0 | I - Informal Settlement | ||
6. | 03001 | Other | 19100269 O03 IV | 04/10/2015 | 11/30/2015 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
At 7:00 a.m. on October 23, 2014, an employee placed test leads on the high and low side transformer bushing for DOBLE testing. The DOBLE testing device energized the test leads and the transformer bushing contacts while the employee was on top of the transformer. The employee was within the minimum approach distance of the live conductors. The conductors were energized by 10kV and 300mA. The employee's hand contacted a high side bushing contact plate on the transformer without an insulated glove and the employee was electrocuted.
Keywords: Electrical, Electrocuted, Protective Clothing
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1003042.015 | 35 | M | Fatality | Electricians' apprentices |