Powered by GoogleTranslate

Inspection Detail

Inspection: 100075993 - Quality Personnel, Inc.

Inspection Information - Office: Columbus Area Office

 

Inspection Nr: 100075993
Report ID: 0522500
Date Opened: 11/03/1986

Site Address:
Quality Personnel, Inc.
3980 Groves Road
Columbus, OH 43227

Mailing Address:
1577 South Parsons Avenue, Columbus, OH 43207

Union Status: NonUnion

SIC:7361

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/12/1986

Emphasis:

Case Closed: 03/16/1987


Related Activity
Type Activity Nr Safety Health
Accident 360681332
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100219 F03 12/11/1986 01/12/1987 $0 $0 $0 -  
2. 01002 Other 19100303 G02 I 12/11/1986 12/14/1986 $0 $0 $0 -  
3. 01003 Other 19100303 G02 II 12/11/1986 12/14/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14570246
Event: 11/01/1986
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

TWO EMPLOYEES WERE REMOVING A TAKE-UP REEL OF INSULATION FROM THE END OF A SLITTING MACHINE. THE SPINDLE IN THE MIDDLE OF THE ROLL WAS ABOUT 6 FEET LONG. A 10-INCH-BY-7-INCH PANELBOARD WAS MOUNTED ON THE SIDE OF THE SLITTING MACHINE AT A HEIGHT OF 19.5 INCHES FROM THE FLOOR. THE COVER FOR THE PANELBOARD HAD BEEN REMOVED BECAUSE THE CIRCUIT BREAKER INSIDE HAD TO BE RESET REPEATEDLY. (THE BREAKER COULD BE RESET WITH THE COVER IN PLACE, BUT THE EMPLOYEES DID NOT REALIZE THAT.) THE LEG OF ONE OF THE EMPLOYEES CONTACTED CIRCUIT PARTS EXPOSED AS A RESULT OF THE MISSING COVER AND ENERGIZED AT 240 VOLTS. THE EMPLOYEE, WHO WAS IN CONTACT WITH THE GROUNDED MACHINE, WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI V, ELECTROCUTED, PANELBOARD, UNGUARDED LIVE PARTS, CIRCUIT BREAKER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 100075993 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close