Accident Summary Nr: 968321 - ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU WIRE

Accident Summary Nr: 968321 -- Report ID: 0953220 -- Event Date: 12/11/1989
Inspection NrDate OpenedSICNAICSEstablishment Name
10466929612/12/198917410M J Di Biase - Simmons Contracting
Inspection NrDate OpenedSICNAICSEstablishment Name
10467284512/12/198917310Dynalectric Company Of Nevada
Inspection NrDate OpenedSICNAICSEstablishment Name
10466928812/12/198915420Marnell Corrao Associates, Inc.

Abstract: AN EMPLOYEE WAS LEAVING HIS ASSIGNED WORK AREA. HIS PATH OF TRAVEL TOOK HIM PAST A 600-AMPERE, 480-VOLT (PHASE-TO-PHASE), FREESTANDING ELECTRICAL SWITCHBOARD. THE SWITCHBOARD DID NOT HAVE A COVER AND WAS NOT DEAD-FRONT. DIRECTLY IN FRONT OF THE SWITCHBOARD, 11 INCHES AWAY, WAS A WOODEN BOX THAT HAD BEEN PLACED OVER A D-C POWER CONVERTER. THE EMPLOYEE WAS CARRYING A 4-FOOT WOOD LADDER, WHICH HAD A LENGTH OF STEEL TIE WIRE WRAPPED AROUND ITS SIDE RAIL. WHEN THE EMPLOYEE SQUEEZED BETWEEN THE SWITCHBOARD AND THE BOX, THE TIE WIRE CONTACTED THE 480-VOLT BUS BARS (277 VOLTS TO GROUND). THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK THROUGH HIS LEFT ARM. HE WAS HOSPITALIZED FOR HIS INJURY AND WAS RELEASED AFTER 24 HOURS.

Keywords: METAL WIRE, ELECTRICAL, BUSBAR, ELECTRIC SHOCK, E GI V, UNGUARDED LIVE PARTS

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 104669296 Hospitalized injury Electric Shock Drywall installers
2 104672845 Occupation Not Listed
3 104669288 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.