Accident Summary Nr: 845099 - BURN - ELECTRICAL FAULT IN SUBSTATION

Accident Summary Nr: 845099 -- Report ID: 0521100 -- Event Date: 07/23/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
10305562007/25/199017310Superior Electric Company

Abstract: TWO EMPLOYEES WERE MEASURING LINE-TO-LOAD DISTANCES FOR RETROFITTING A 480-VOLT, 100-AMPERE BREAKER ONTO 200-AMPERE BUS FINGERS ON THE SECONDARY SIDE OF AN ISOLATED TRANSFORMER INSTALLED INDOORS. THEY WERE TAKING THEIR MEASUREMENTS AT AN UNGUARDED, ENERGIZED PANELBOARD IN A MAIN SUBSTATION. AN EXPLOSION AND FIRE OCCURRED, AND BOTH EMPLOYEES WERE SEVERELY BURNED. TWO 6-FOOT WOODEN FOLDING-TYPE RULES WITH BRASS TIPS AND HINGES WERE FOUND AT THE ACCIDENT SCENE. ONE OF THE RULES WAS SIGNIFICANTLY BURNED. IT WAS BELIEVED THAT AN ELECTRIC ARC OCCURRED WHEN THE TIP OF THE RULE CONTACTED LINE VOLTAGE. THIS CAUSED A FAULT AND AN EXPLOSION. A SECOND EXPLOSION WAS HEARD, AND IT WAS BELIEVED TO HAVE BEEN CAUSED BY A FAULT IN A TRANSFORMER COIL. SEVERE FIRE DAMAGE WAS EVIDENT AT THE OPEN PANELBOARD SECTIONS. THE FAULT CONTINUED THROUGH TWO SECTIONS OF THE 100-AMPERE PANELBOARD, ENDING AT AN ENCLOSED PANELBOARD SECTION. THE FAULT BLEW A HOLE THROUGH THE PANELBOARD COVER. THE 125E PRIMARY FUSES CLEARED THE FAULT. THERE WAS NO SECONDARY FUSE PROTECTION INSTALLED. BOTH EMPLOYEES WERE HOSPITALIZED FOR THEIR INJURIES. (A THIRD EMPLOYEE WAS ALSO INJURED AS A RESULT OF THE ACCIDENT, BUT THE NATURE AND CAUSE OF HIS INJURIES WERE NOT GIVEN IN THE REPORT.)

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, MEASURING DEVICE, POWER LINE WORKER, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 103055620 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 103055620 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
3 103055620 Non Hospitalized injury Concussion Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.