Accident Summary Nr: 840884 - ELECTRIC SHOCK - GROUND FAULT IN CORD SET
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 109637579 | 07/31/1991 | 3315 | 0 | Techalloy Company, Inc. |
Abstract: AN EXTENSION CORD SET THAT WAS USED TO ENERGIZE A RESISTANCE WELDER (A BUTT WELDER) HAD BEEN IMPROPERLY WIRED. THE CORD SET WAS NOT MANUFACTURED, BUT WAS ASSEMBLED IN HOUSE BY UNQUALIFIED PERSONS. DURING THE INITIAL ASSEMBLY, THE CORD SET WAS WIRED CORRECTLY, EXCEPT THAT THE GREEN CONDUCTOR WAS USED AS A CURRENT-CARRYING CONDUCTOR, RATHER THAN AS THE EQUIPMENT GROUNDING CONDUCTOR. LATER, THE CORD CONNECTOR ON THE CORD SET WAS REPLACED. WHEN THIS WAS DONE, THE GREEN CONDUCTOR WAS CONNECTED TO THE EQUIPMENT GROUNDING TERMINAL. A CONTINUITY CHECK WAS NOT PERFORMED ON THE REPAIRED CORD SET. AN EMPLOYEE WAS ELECTROCUTED WHEN HE CONTACTED THE WELDER AFTER THE REPAIRED CORD SET WAS PLUGGED IN.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 109637579 | Fatality | Electric Shock | Occupation not reported |