Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 810101 - ELECTRIC SHOCK - GROUND FAULT IN PORTABLE GENERATOR

Accident Summary Nr: 810101 -- Report ID: 0453710 -- Event Date: 10/04/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
1854267010/04/198817810Mccall Brothers, Inc.

Abstract: AN EMPLOYEE WAS TOUCHING A THE METAL FRAME OF A PORTABLE GENERATOR. AN ABRADED CONDUCTOR INSIDE A PANEL WAS FAULTED TO THE GENERATOR'S FRAME. THE GROUNDING ELECTRODE AND BONDING CONDUCTOR WERE INEFFECTIVE, ALLOWING THE FRAME OF THE GENERATOR TO BECOME ENERGIZED AT A LOW VOLTAGE. THE EMPLOYEE, WHO WAS STANDING ON WET GROUND, WAS ELECTROCUTED.

Keywords: ELECTRICAL, ELECTROCUTED, E C, GROUND FAULT, BONDING, ELECTRIC CONDUCTOR, SYSTEM GROUNDING, ELECTRIC GENERATOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18542670 Fatality Electric Shock Drillers, earth

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.