Accident Report Detail
Accident Summary Nr: 676833 - BURN - ELECTRICAL FAULT IN ELECTRICAL CABINET
Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
---|---|---|---|---|
108224288 | 05/24/1990 | 1731 | 0 | Electrical Construction Company |
Abstract: Two electricians were routing conductors behind the vertical busbars of a large floor-mounted, high-ampacity circuit breaker cabinet. As of them fed a grounding conductor to his coworker, the conductor slipped and contacted one of the 277-volt busbars, which had not been deenergized. A phase-to-phase electrical fault occurred, and the ensuing electric arc burned both employees. One of the injured employees was able to use a portable telephone to call for assistance under his employer's emergency plan. The employees were hospitalized at a burn center.
Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 108224288 | Hospitalized injury | Burn/Scald(Heat) | Supervisors; electricians & power transm. install. | ||
2 | 108224288 | Hospitalized injury | Burn/Scald(Heat) | Supervisors; electricians & power transm. install. |