Accident Summary Nr: 606889 - BURN - ELECTRICAL FAULT AND EXPLOSION

Accident Summary Nr: 606889 -- Report ID: 0418100 -- Event Date: 10/12/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
10121588710/19/198717310Maner'S & Sons Electrical Company, Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
10121589510/19/198717310Southeast Electric, Inc.

Abstract: DURING A CONSTRUCTION PROJECT TO REMODEL AN EXISTING BUILDING INTO A PHARMACY, AN EMPLOYEE WAS GOING TO ADD A CONDUIT TO AN EXISTING PANELBOARD WHILE IT REMAINED ENERGIZED. HE DRILLED INTO THE ENERGIZED PANELBOARD, AND THE DRILL CONTACTED LIVE PARTS. THE RESULTING FAULT TRIPPED THE MAIN CIRCUIT BREAKER, AND AT LEAST ONE OF THE THREE FUSES ON THE SERVICE POLE OPENED. ONE OR MORE OF THE THREE PHASE CONDUCTORS TO THE PANELBOARD REMAINED ENERGIZED. THE EMPLOYEE ATTEMPTED TO RESET THE MAIN CIRCUIT BREAKER, BUT COULD NOT DO SO. TWO OTHER EMPLOYEES REMOVED THE COVER FROM THE PANELBOARD AND, WITH ONLY A FLASHLIGHT TO PROVIDE ILLUMINATION, TRIED TO REPAIR THE MAIN CIRCUIT BREAKER. A FAULT OCCURRED, AND THE RESULTING ELECTRICAL EXPLOSION BURNED SIX EMPLOYEES. THREE OF THEM WERE HOSPITALIZED FOR THEIR INJURIES.

Keywords: BURN, CLOTHING, ELECTRICAL, PANELBOARD, ELECTRICAL WORK, LOCKOUT, E C, CIRCUIT BREAKER, ELECTRICAL FAULT, BLIND REACHING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 101215887 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 101215887 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
3 101215895 Hospitalized injury Burn/Scald(Heat) Occupation not reported
4 101215895 Hospitalized injury Burn/Scald(Heat) Occupation not reported
5 101215895 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
6 101215895 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.