Accident Summary Nr: 606533 - PROBABLE ELECTRIC SHOCK - GROUND FAULT IN HOIST

Accident Summary Nr: 606533 -- Report ID: 0418100 -- Event Date: 10/02/1989
Inspection NrDate OpenedSICNAICSEstablishment Name
1831804810/04/198922810The Bibb Company

Abstract: AN 18-YEAR OLD EMPLOYEE COLLAPSED DEAD ON THE JOB. HE HAD BEEN SEEN, JUST BEFORE HIS COLLAPSE, PULLING A REEL-TYPE MONORAIL HOIST BY ITS HOOK. UPON INSPECTION OF THE HOIST, ITS EQUIPMENT GROUNDING CONDUCTOR WAS FOUND NOT TO HAVE BEEN CONNECTED TO ITS TERMINAL, AND A METAL CLAMP USED TO SECURE THE REEL CABLE TO THE HOIST MOTOR WAS FOUND TO HAVE CUT THROUGH THE OUTER JACKET OF THE CABLE AND THROUGH THE INSULATION ON THE BLACK CONDUCTOR. THE CLAMP WAS ALSO FOUND TO BE IN CONTACT WITH THE EXPOSED PORTION OF THE CIRCUIT CONDUCTOR. THUS, AT THE TIME OF THE INCIDENT, THE FRAME OF THE HOIST WAS ENERGIZED. THE AUTOPSY PERFORMED ON THE DECEASED EMPLOYEE FOUND NO BURN MARKS AS EVIDENCE OF ELECTROCUTION, BUT DID FIND A PRE-EXISTING HEART CONDITION. AS A RESULT, THE AUTOPSY REPORT STATED THAT THE CAUSE OF DEATH "COULD NOT BE ABSOLUTELY DETERMINED."

Keywords: ELECTRICAL, ELECTRIC CABLE, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18318048 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close