Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 566109 - BURN - ELECTRICAL FAULT IN ELECTRICAL BOX

Accident Summary Nr: 566109 -- Report ID: 0636900 -- Event Date: 02/25/1992
Inspection NrDate OpenedSICNAICSEstablishment Name
11036222502/25/199217310Summit Electric Of Texas, Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
11036224102/25/199273710International Business Machines, Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
11036223302/25/199265120Maguire Thomas Partners
Inspection NrDate OpenedSICNAICSEstablishment Name
11036221702/26/199217310Efp Electrical Contractors, Inc.

Abstract: A MAINTENANCE CREW OF THREE ELECTRICIANS WAS REPLACING A 480-VOLT, 400-AMPERE MAIN DISCONNECT BOX IN AN ELECTRICAL CONTROL ROOM. THE ELECTRIC POWER FOR THE DISCONNECT WAS RESTORED AFTER THE BOX WAS PLUGGED INTO THE BUS DUCT RISER. TWO OF THE ELECTRICIANS WERE ATTACHING THE CONDUCTORS TO THE LUGS INSIDE THE BOX. A BOLT ON ONE OF THE LUGS SHEARED OFF, AND A PIECE OF THE BOLT DROPPED TO THE BOTTOM OF THE DISCONNECT BOX. ONE OF THEM TRIED TO RETRIEVE THE PIECE AND CONTACTED AN ENERGIZED PART WITHIN THE ENCLOSURE. THIS CAUSED AN ELECTRICAL FAULT, AND THE ENSUING ELECTRIC ARC BURNED THE EMPLOYEE ON HIS FACE AND RIGHT ARM. HE WAS HOSPITALIZED FOR HIS INJURIES. THE SECOND ELECTRICIAN SUSTAINED BURNS OVER MOST OF HIS FACE.

Keywords: ELECTRIC ARC, ELECTRICAL, BURN, CLOTHING, ELECTRICIAN, LOCKOUT, ELECTRICAL BOX, E GI IV, ELECTRICAL FAULT, ELECTRICAL WORK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 110362225 Non Hospitalized injury Burn/Scald(Heat) Electricians
2 110362241 Occupation Not Listed
3 110362233 Occupation Not Listed
4 110362217 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.