Abstract: At approximately 2:45 p.m. on June 5, 2007, Employee #1, a journeyman electrician, was troubleshooting and performing diagnostics to determine the source of intermittent power failures at a senior living facility in Tarzana, CA. He had isolated the problem to a 480 volt circuit breaker in the electrical room. The circuit breaker is normally enclosed by a panel to protect against accidental contact. Employee #1 had removed his gloves when he noticed the surface as well as the side of the circuit breaker were hot to the touch. He was using a screwdriver to re-install the cover on the panel when it fell onto the exposed energized sections of the panel. This caused an electrical arc from phase-to-phase and produced an electrical flash. Employee #1 sustained serious burns and was transported to Grossman Burn Center, where he was hospitalized for seven days and underwent skin grafts. Employee #1 was working alone at the time of the incident. The employer was cited for a serious, accident-related violation of T8CCR 2320.2(a), for failing to use insulated tools in accordance with ASTM 1505-94.

Keywords: BURN, ELECTRIC ARC, REPAIR, ELECTRICAL, INSULATED TOOL, WORK RULES, CONSTRUCTION, ELECTRICAL WORK, ELECTRICAL CABINET
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Multi-family dwelling Other Under $50,000 3

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 310197660 Hospitalized injury Burn/Scald(Heat) Misc. electrical & electronic equipment repairers Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Interior plumbing, ducting, electrical work
Fatality Cause: Fire/explosion

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.